The Schneider Electric MGN25146 is a C60H miniature circuit-breaker from the Multi9 range, built for distribution duty in 35 mm symmetrical DIN-rail panels. Four poles, D-curve thermal-magnetic trip, rated 20 A at 50 °C per EN/IEC 60947-2.
Breaking capacity and voltage ratings
Rated breaking capacity (Icu) reaches 30 kA at 240 V AC phase-to-phase, 15 kA at 415 V, and 10 kA at 440 V — all per EN/IEC 60947-2. Service breaking capacity (Ics) is 50 % of Icu at each voltage level, so at 240 V that is 15 kA. The rated operational voltage (Ue) is 440 V AC, with a 240 V phase-to-phase option. These figures govern selectivity coordination downstream.
Snaps onto 35 mm symmetrical DIN rail. Fixed mounting, toggle control, ON/OFF indication on the front. IP20 finger-safe front.
Listed as current production.