MGN60524 key specifications
ParameterValue
Control typeToggle
Network typeAC
Range of productC60
Product or component typeMiniature circuit-breaker
[Ue] rated operational voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Current20 A at 50 °C conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description2P
Number of protected poles2
Utilisation categoryCategory A conforming to EN/IEC 60947-2

All specifications

MGN60524 additional specifications
ParameterValue
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Mounting modeFixed
Mounting support35 mm symmetrical DIN rail
Wire stripping lengthPower circuit: 14 mm
Connections - terminalsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width36 mm
Height81 mm
Electrical durability10000 cycles conforming to EN/IEC 60947-2
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeMulti9
Curve codeD
9 mm pitches4
Local signallingON/OFF indication
Device short nameC60N
Tightening torquePower circuit: 2 N.m
Device applicationDistribution
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...80 °C
Ambient air temperature for operation-30...70 °C
Comb busbar and distribution block compatibilityTop or bottom: YES
MPN