Schneider Electric MGN60536 — Miniature Circuit Breakers (MCB)

MGN60536 C60N MCB, 3P D-Curve 16A, 20kA, Multi9

MPNMGN60536
Obsolete

Schneider Electric C60N Multi9 series, MGN60536, 3-pole D-curve miniature circuit breaker, 16 A rated, 20 kA breaking capacity at 240 V AC, thermal-magnetic trip, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN60536 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN60536 — Ratings
ParameterValue
Rated current (In)16 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN60536 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN60536 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN60536 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN60536 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Panel-builder commissioning notes

The MGN60536 is a C60N miniature circuit breaker from the Multi9 range, a 3-pole unit with a D-curve thermal-magnetic trip set at 16 A. It is rated for distribution duty under EN/IEC 60947-2, Category A, meaning it is not intended for motor switching but for cable and equipment protection in final subcircuits. The 20 kA Icu at 240 V AC phase-to-phase gives it a high fault-clearing ceiling for a 3-module-wide (54 mm) DIN-rail device; the service breaking capacity Ics is 75 % of that figure (15 kA at 240 V), so it can reclose after a fault at that level without replacement. The D-curve magnetic trip operates at 12 x In ±20 %, which suits loads with a high inrush — small transformers, power supplies, or lighting ballasts — where a C-curve would nuisance-trip.

The 54 mm width occupies 6 x 9 mm pitches. IP20 finger-safe terminals are standard for enclosed panel use. The toggle provides local ON/OFF indication and a contact position indicator confirms isolation status — the breaker is certified for isolation duty per EN/IEC 60947-2.

Frequently asked questions

What are the key ratings of MGN60536?

It is a 3-pole D-curve MCB rated 16 A at 50 °C, with a breaking capacity of 20 kA Icu at 240 V AC and 10 kA at 415 V AC, conforming to EN/IEC 60947-2.

What is the D-curve magnetic trip threshold?

The magnetic trip operates at 12 x In ±20 %, meaning it will trip instantaneously between roughly 15.4 A and 23 A for a 16 A breaker.

Where can I buy MGN60536?

The MGN60536 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
MGN60536