Skip to main content
Schneider Electric MGN60546 — Miniature Circuit Breakers (MCB)

MGN60546 C60N MCB, 4P D-Curve 4A, 20kA, Multi9

MPNMGN60546
Obsolete

Schneider Electric Multi9 C60N series, MGN60546 miniature circuit breaker, 4-pole, D-curve, 4 A rated current, 20 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN60546 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN60546 — Ratings
ParameterValue
Rated current (In)4 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration4P
Number of protected poles4
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN60546 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN60546 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width72 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches8
MGN60546 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN60546 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric MGN60546 is a C60N miniature circuit breaker from the Multi9 range, configured as a 4-pole (4P) unit with a D-curve trip characteristic and a 4 A rated current (In) at 50 °C per EN/IEC 60947-2. Its interrupting capacity reaches 20 kA Icu at 240 V AC (phase-to-phase, 50/60 Hz), 10 kA at 415 V AC, and 6 kA at 440 V AC, all conforming to EN/IEC 60947-2. The corresponding service breaking capacity (Ics) is 75 % of Icu at each voltage level — 15 kA, 7.5 kA, and 4.5 kA respectively — meaning the breaker can be reclosed after clearing a fault at those levels without immediate replacement.

Standards, mounting, and environment

Designed for fixed mounting on a 35 mm symmetrical DIN rail, the MGN60546 occupies 8 x 9 mm pitches (72 mm width) in the enclosure. The 73 mm depth and 81 mm height fit standard distribution board layouts. Rated IP20 (finger-safe terminals) per EN/IEC 60947-2, suitable for installation in a dry indoor panel. Pollution degree 3 per the same standard, so it tolerates conductive pollution typical of industrial control cabinets. The breaker carries a suitability-for-isolation marking (yes, per EN/IEC 60947-2) and a visible contact position indicator (ON/OFF indication) for safe isolation verification during maintenance.

D-curve application context

In a distribution board, this 4 A 4P unit protects a three-phase circuit with neutral, where the D-curve prevents nuisance tripping on the magnetizing inrush of a small transformer or the starting surge of a motor contactor coil. Rated for category A utilization (EN/IEC 60947-2), meaning it is not specifically intended for selectivity under short-circuit conditions with downstream breakers, though practical coordination is still achievable with careful selection.

Frequently asked questions

How do I get current pricing and availability for MGN60546?

Submit an RFQ through this listing. Pricing and stock levels are confirmed at quote time through the authorized distribution channel — no published price or stock count is maintained on this page.

What is the breaking capacity of MGN60546 at 240 V?

The MGN60546 has a rated ultimate breaking capacity (Icu) of 20 kA at 240 V AC (phase-to-phase, 50/60 Hz) per EN/IEC 60947-2. The service breaking capacity (Ics) at that voltage is 15 kA (75 % of Icu).

What does the D-curve on MGN60546 mean?

The D-curve means the magnetic trip operates at 12 x In (± 20 %), so for this 4 A breaker, instantaneous tripping occurs between roughly 38 A and 58 A. This is designed for loads with high inrush, such as transformers, welding sets, and motor starters.

What compliance documentation does Schneider provide for MGN60546?

The MGN60546 is certified to EN/IEC 60947-2. It carries a suitability-for-isolation marking and pollution degree 3 rating per that standard. Specific RoHS, REACH, and UL documentation should be requested at quote time; the product record does not list those separately.

MPN