Skip to main content
Schneider Electric MGN60635 — Miniature Circuit Breakers (MCB)

MGN60635 C60H Miniature Circuit-Breaker, 3P, C-Curve, 2 A, 3

MPNMGN60635
Obsolete

Schneider Electric Multi9 C60H series, MGN60635 miniature circuit-breaker, 3 poles, C-curve, 2 A rated current, 30 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN60635 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN60635 — Ratings
ParameterValue
Rated current (In)2 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 40 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN60635 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8.5 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN60635 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN60635 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN60635 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The MGN60635 is a 3-pole miniature circuit-breaker (MCB) from the Schneider Electric Multi9 C60H series, rated 2 A at 50 °C with a C-curve trip characteristic (magnetic tripping at 8.5 x In ±20 %). It is designed for distribution applications and uses thermal-magnetic trip technology to protect branch circuits against overload and short-circuit currents. The breaking capacity is 30 kA Icu at 240 V AC (phase-to-phase, 50/60 Hz) per EN/IEC 60947-2, with 15 kA at 415 V AC, 10 kA at 440 V AC, and 25 kA at 125 V DC. The service breaking capacity Ics is 50 % of Icu at AC voltages (15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V) and 100 % (40 kA) at 125 V DC. Mounts on a 35 mm symmetrical DIN rail (6 module pitches of 9 mm each) and accepts tunnel-type terminals for 1–25 mm² conductors. The IP20 rating means it is suitable for installation inside an enclosure — not for wet or washdown areas.

For a 2 A rating, that means magnetic pickup between 13.6 A and 20.4 A. The 10 kA at 440 V AC covers three-phase line-to-line faults at standard industrial voltages.

The IP20 terminals and pollution degree 3 rating are part of the same standard certification.

MPN