The Schneider Electric MGN60636 is a C60H miniature circuit breaker from the Multi9 range, rated 3 A at 50 °C with a C trip curve and three protected poles. The C curve means magnetic tripping occurs between 5 and 10 times the rated current — here 8.5 x In ±20 % — making it suited for moderate inrush loads like small motors or lighting circuits where a B curve would nuisance-trip but a D curve would delay too long.
For DC networks, the 25 kA Icu at 125 V DC covers most industrial control and telecom battery-backed supplies. The thermal-magnetic trip unit handles overloads (thermal bimetal) and short-circuits (magnetic solenoid) in one package.
Strip 14 mm of insulation for power connections. IP20 finger-safe protection is standard for enclosed panels. The toggle actuator provides local ON/OFF indication and manual switching.