Skip to main content
Schneider Electric MGN60643 — Miniature Circuit Breakers (MCB)

MGN60643 C60H MCB, 3P C-Curve 32 A, 30 kA Breaking

MPNMGN60643
Obsolete

Schneider Electric Multi9 C60H series, MGN60643 miniature circuit-breaker, 3-pole, C-curve, 32 A, 30 kA breaking capacity at 240 V AC, DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN60643 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN60643 — Ratings
ParameterValue
Rated current (In)32 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 40 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN60643 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8.5 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN60643 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid
Terminal tightening torquePower circuit: 3.5 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN60643 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN60643 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The MGN60643 is a 3-pole C60H miniature circuit-breaker from the Multi9 range, rated 32 A at 50 °C per EN/IEC 60947-2. Breaking capacity is 30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V AC, and 10 kA at 440 V AC. The Ics (service breaking capacity) is 50 % of Icu at those voltages — 15 kA at 240 V AC, 7.5 kA at 415 V AC, 5 kA at 440 V AC — and 40 kA at 125 V DC (100 %). That means after clearing a fault at the Ics level the breaker can be reclosed without immediate replacement, which matters for uptime in industrial distribution. Rated operational voltage is 440 V AC 50/60 Hz phase-to-phase, and the breaker is also rated for DC networks — 125 V DC with 25 kA Icu. The thermal-magnetic trip unit covers both overload and short-circuit protection; earth-leakage protection requires a separate block (Vigi or similar).

The 3-pole body is 54 mm wide, 81 mm tall, 73 mm deep. Tunnel terminals accept 1.5...35 mm² rigid or flexible. IP20, pollution degree 3. Comb busbars and distribution blocks can feed top or bottom. The toggle gives local ON/OFF indication with a contact position indicator. Isolation-suitable per EN/IEC 60947-2 — use as a disconnecting means for the downstream circuit.

Frequently asked questions

What is the breaking capacity of MGN60643?

30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V AC, 10 kA at 440 V AC, and 25 kA at 125 V DC, all per EN/IEC 60947-2.

What is the rated current and curve of MGN60643?

32 A at 50 °C, C-curve (magnetic trip at 8.5 x In ±20 %).

MPN
MGN60643