Skip to main content
Schneider Electric MGN60889 — Miniature Circuit Breakers (MCB)

MGN60889 C60N 3P C-Curve MCB, 2 A, 20 kA Icu at 240 V

MPNMGN60889
Obsolete

Schneider Electric Multi9 C60N, 3P, C-curve, 2 A, 20 kA Icu at 240 V AC, thermal-magnetic miniature circuit breaker.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN60889 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN60889 — Ratings
ParameterValue
Rated current (In)2 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN60889 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8.5 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN60889 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN60889 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN60889 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric MGN60889 is a C60N miniature circuit breaker from the Multi9 range, a 3-pole unit with a C-curve and a 2 A rated current at 50 °C per EN/IEC 60947-2. The C-curve (magnetic trip at 8.5 x In ±20 %) is the standard choice for motor-starting and moderate inrush loads, so it fits general distribution and light motor branch circuits where the startup surge won't nuisance-trip a B-curve.

The 3-pole body is 54 mm wide (6 x 9 mm pitches), 81 mm tall, and 73 mm deep, so it fits a standard distribution board without crowding the adjacent breakers. Strip 14 mm of insulation for a clean connection.

The Ics is 75 % of Icu at the same voltage, meaning it can be reclosed after a fault at 15 kA.

Frequently asked questions

What is the breaking capacity of MGN60889?

The MGN60889 has a 20 kA Icu at 240 V AC phase-to-phase (EN/IEC 60947-2), 10 kA Icu at 415 V AC, and 6 kA Icu at 440 V AC. The Ics (service breaking capacity) is 75 % of Icu at each voltage level.

What compliance documentation does MGN60889 carry?

The breaker is certified to EN/IEC 60947-2, with a pollution degree of 3 per that standard. It carries an IP20 degree of protection. The evidence does not list RoHS, REACH, or UL documentation specifically; verify with the supplier at quote time if those are required for your jurisdiction.

MPN
MGN60889