The MGN60892 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range, rated 6 A at 50 °C per EN/IEC 60947-2 with a C curve. Three protected poles, thermal-magnetic trip unit, toggle control with ON/OFF indication and a contact position indicator. Breaking capacity hits 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V. Service breaking capacity (Ics) is 75 % of those figures — 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. Magnetic tripping threshold is 8.5 x In ± 20 %. Pollution degree 3 rated. Dimensions: 81 mm high, 54 mm wide, 73 mm deep. 6 module pitches (9 mm each). IP20 finger protection. Earth-leakage protection requires a separate block — no holes in the box for that function, but the breaker is comb busbar compatible top or bottom.
The C curve (magnetic trip at 8.5 x In ± 20 %) means this breaker handles moderate inrush — typical for motor starters, small transformers, and lighting banks in distribution panels. The 6 A rating at 50 °C is the continuous current; no derate needed at that ambient, but above 50 °C the thermal element shifts. Ics at 75 % (15 kA) is the rating for repeated fault clearing without replacement. For a 3-pole DC network application, verify the DC voltage rating against your system; the listed ratings are AC phase-to-phase.
Panel integration
Snaps onto 35 mm symmetrical DIN rail — standard for any enclosure. 6 module pitches (54 mm wide) means it occupies six 9 mm slots on the rail. Comb busbar compatible top or bottom, so daisy-chaining multiple breakers in a row is straightforward.