Skip to main content
Schneider Electric MGN60893 — Miniature Circuit Breakers (MCB)

MGN60893 C60N MCB, 3P C-curve 10 A, 20 kA breaking

MPNMGN60893
Obsolete

Schneider Electric Multi9 C60N miniature circuit-breaker, MGN60893, 3P, C-curve, 10 A, 20 kA Icu at 240 V AC, thermal-magnetic trip, DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN60893 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN60893 — Ratings
ParameterValue
Rated current (In)10 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN60893 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8.5 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN60893 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN60893 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN60893 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The MGN60893 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range, rated 10 A at 50 °C with a C trip curve and 3 poles. It breaks 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V, all per EN/IEC 60947-2. The 3-pole block takes 6 module pitches (54 mm wide), so it fits a standard 6-M slot in a distribution board. Torque to 2 N·m on the power circuit. Strip 14 mm of insulation.

Built to EN/IEC 60947-2, Category A, with pollution degree 3. Suitable for isolation (contact position indicator on the toggle). Service breaking capacity (Ics) is 75% of Icu: 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. Electrical durability 10,000 cycles, mechanical 20,000 cycles. Earth-leakage protection via a separate block.

Frequently asked questions

Where can I buy MGN60893 and get a price?

We source the MGN60893 to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ through this listing.

What is the breaking capacity of MGN60893?

The MGN60893 has a rated breaking capacity (Icu) of 20 kA at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V, all per EN/IEC 60947-2.

What is the closest alternative to MGN60893 in the same family?

Within the C60 range, the main difference is the curve code — this is a C curve. A B-curve sibling would trip magnetically at a lower threshold (3.2–4.8 x In), better for resistive loads or long cable runs; a D-curve sibling trips at 10–14 x In, suited for high-inrush loads like large motors or transformers. The physical footprint and breaking capacities are otherwise identical.

What compliance documentation does Schneider provide for MGN60893?

The MGN60893 is certified to EN/IEC 60947-2. Schneider Electric typically provides a Declaration of Conformity (CE) and may supply UL/CSA documentation depending on the variant. Specific documentation is available on request at quote time.

MPN