The MGN60895 is a Schneider Electric C60N miniature circuit breaker from the Multi9 range, configured as a 3-pole, 20 A unit with a C trip curve. It's designed for distribution board duty and snaps onto 35 mm symmetrical DIN rail, making it a standard fit for panel builds where the C60 family is already specced. Rated 20 A at 50 °C per EN/IEC 60947-2, with a breaking capacity of 10 kA Icu at 415 V AC phase-to-phase. That's the number to check for fault-clearing capability on your supply side — at 240 V it rises to 20 kA Icu. Curve C means magnetic tripping occurs between 5 and 10 times rated current; the datasheet fixes it at 8.5 x In ± 20 %.
This is a 3-pole breaker for DC network applications, so confirm your system voltage and polarity requirements against the rated operational voltage of 440 V AC / 240 V AC phase-to-phase.
Installation and compliance notes
Mounts fixed on 35 mm DIN rail. Strip length 14 mm. The tunnel-type terminals are compatible with comb busbars top or bottom, which speeds up panel wiring when feeding multiple breakers. Pollution degree 3 per EN/IEC 60947-2 means it's rated for conductive pollution in industrial atmospheres. Mechanical durability rated at 20,000 cycles, electrical durability at 10,000 cycles. Ambient operating range -30…70 °C, storage -40…80 °C. The ON/OFF indication on the toggle and contact position indicator give visual confirmation of breaker state without needing to meter the load side.