C60N 1 A C-curve 4P MCB — panel fit and protection profile
The 1 A rating suits low-current loads — control transformers, signal supplies, or lighting circuits drawing under 1 A continuous. Breaking capacity is 20 kA Icu at 240 V AC phase-to-phase, derating to 10 kA at 415 V and 6 kA at 440 V. The service breaking capacity (Ics) is 75 % of Icu at each voltage level — 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V — meaning the breaker can be reclosed after a fault at those levels without immediate replacement, which matters for selectivity coordination studies.
Tighten to 2 N.m. Earth-leakage protection requires a separate block (not integrated).