Schneider Electric MGN60907 — Miniature Circuit Breakers (MCB)

MGN60907 C60N MCB, 4P, C-Curve, 16 A, 20 kA, Multi9

MPNMGN60907
Obsolete

Schneider Electric C60N Multi9 miniature circuit-breaker, MGN60907, 4 poles, C-curve, 16 A, 20 kA Icu at 240 V AC, thermal-magnetic trip, 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN60907 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN60907 — Ratings
ParameterValue
Rated current (In)16 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration4P
Number of protected poles4
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN60907 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8.5 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN60907 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width72 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches8
MGN60907 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN60907 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The MGN60907 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range, rated 16 A at 50 °C with a C-curve trip characteristic.

Rated 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V per EN/IEC 60947-2. The service breaking capacity Ics is 75 % of Icu at each voltage level — 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. That 75 % ratio means the breaker can be reclosed after a fault at that level without immediate replacement, which matters for uptime in a distribution board where a downstream fault is cleared and the feeder needs to come back online.

Trip unit and coordination

Thermal-magnetic trip with a magnetic threshold of 8.5 x In ±20 %. For a 16 A breaker that puts the instantaneous trip between roughly 109 A and 163 A. The C-curve is the standard choice for moderate inrush loads — motor starters, small transformers, banks of LED drivers — where the magnetic pickup needs to ride through the start surge without nuisance tripping but still clear a hard short fast.

Snaps onto 35 mm symmetrical DIN rail. Occupies 8 x 9 mm pitches (72 mm wide) for the 4-pole body. IP20 finger-safe front — standard for enclosed distribution boards.

Frequently asked questions

Where can I buy MGN60907 and how do I get a price?

The MGN60907 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is MGN60907's breaking capacity at 240 V AC?

The MGN60907 has a rated ultimate breaking capacity Icu of 20 kA at 240 V AC phase-to-phase, with a service breaking capacity Ics of 15 kA (75 %) at the same voltage.

What terminals does the MGN60907 accept?

Tunnel-type terminals accept 1 to 25 mm² rigid or flexible conductors, with a wire strip length of 14 mm and a tightening torque of 2 N·m.

MPN