Skip to main content
Schneider Electric MGP0254X — Miniature Circuit Breakers (MCB)

Schneider Electric MGP0254X PowerPacT 4 MCCB, 25A, 4P, 415V,

MPNMGP0254X
Obsolete

Schneider Electric PowerPacT 4, MGP0254X, molded case circuit breaker, 4P, 25 A, 415 V AC, TM-D thermal-magnetic trip unit, LI protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP0254X — Identification
ParameterValue
Product range (series)PowerPacT 4
Product/component typeCircuit breaker
Device applicationDistribution
MGP0254X — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V
Rated impulse withstand voltage (Uimp)8 kV
Utilisation categoryCategory A
MGP0254X — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In
Mechanical durability (cycles)50000 cycles
MGP0254X — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
MGP0254X — Approvals
ParameterValue
StandardsBS EN 60947-2
MGP0254X — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz
MGP0254X — Specifications
ParameterValue
Trip unit protection functionsLI

Product details

The Schneider Electric MGP0254X is a 4-pole molded case circuit breaker from the PowerPacT 4 range, rated 25 A at 40 °C with a TM-D thermal-magnetic trip unit providing LI protection — thermal overload (L) and magnetic short-circuit (I). It is designed for distribution applications in 250 A or 400/630 A panelboards, panel-mounted on a backplate, and can be installed horizontally or vertically. The toggle control type gives a clear visual indication of the contact position.

The MGP0254X is certified to BS EN 60947-2, the standard for low-voltage switchgear and controlgear — specifically for circuit breakers. It is suitable for isolation per that standard, meaning it provides a visible break and meets the disconnection requirements for safe maintenance.

Frequently asked questions

How do I get current pricing and availability for MGP0254X?

Submit an RFQ. We source the MGP0254X through independent distribution channels — availability and current pricing are confirmed at quote time.

What is MGP0254X's listed standards (BS EN 60947-2) on this component line?

The MGP0254X is certified to BS EN 60947-2, the standard for low-voltage circuit breakers, and is suitable for isolation per that standard.

What is MGP0254X's listed control type (Toggle) on this component line?

The MGP0254X uses a toggle control type for manual operation and visual indication of the contact position.

MPN