Skip to main content
Schneider Electric MGP0404X — Miniature Circuit Breakers (MCB)

Schneider Electric MGP0404X PowerPacT 4 MCCB, 40A 4P 36kA

MPNMGP0404X
Obsolete

Schneider Electric PowerPacT 4, MGP0404X, Molded Case Circuit Breaker, 4P, 40 A, 415 V AC, 36 kA Icu, thermal-magnetic TM-D trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP0404X — Identification
ParameterValue
Product range (series)PowerPacT 4
Product/component typeCircuit breaker
Device applicationDistribution
MGP0404X — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V
Rated impulse withstand voltage (Uimp)8 kV
Utilisation categoryCategory A
MGP0404X — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In
Mechanical durability (cycles)50000 cycles
MGP0404X — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
MGP0404X — Approvals
ParameterValue
StandardsBS EN 60947-2
MGP0404X — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz
MGP0404X — Specifications
ParameterValue
Trip unit protection functionsLI

Product details

The Schneider Electric MGP0404X is a PowerPacT 4 molded case circuit breaker (MCCB) with 4 poles (4P), rated 40 A at 40 °C, and designed for distribution in panelboards up to 250 A or 400/630 A. It uses a thermal-magnetic TM-D trip unit providing LI protection — thermal for overload (adjustable 28...40 A) and magnetic for short-circuit.

The MGP0404X is listed as obsolete by Schneider Electric.

The MGP0404X is certified to BS EN 60947-2, the standard for low-voltage switchgear and controlgear — specifically for circuit breakers. It is suitable for isolation per that standard, meaning it provides a visible break and meets the isolation gap requirements. Rated impulse withstand voltage is 8 kV, and insulation voltage is 800 V.

Panel-mounted via backplate, accepting horizontal or vertical orientation. Occupies 4 modules of 35 mm width. The toggle control and 4-pole configuration are straightforward for a panel builder — wire the line and load sides, set the thermal adjustment dial between 28 and 40 A to match the protected conductor, and torque to the nameplate values.

Frequently asked questions

What are the key ratings of the MGP0404X?

Rated 40 A at 40 °C, 4-pole, 415 V AC 50/60 Hz, with 36 kA Icu and Ics short-circuit breaking capacity. Thermal-magnetic TM-D trip unit with LI protection, adjustable thermal range 28...40 A.

What standard is the MGP0404X certified to?

BS EN 60947-2 for low-voltage switchgear and controlgear circuit breakers. It is also suitable for isolation per that standard.

MPN