Skip to main content
Schneider Electric MGP1004XFO — Miniature Circuit Breakers (MCB)

Schneider Electric MGP1004XFO PowerPacT 4 Frame, 100A 4P 50k

MPNMGP1004XFO
Obsolete

Schneider Electric PowerPacT 4 series, basic frame MGP1004XFO, 100 A, 4 poles, 50 kA Icu at 415 V AC, without trip unit, grey, IP40, panel-mounted.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP1004XFO — Identification
ParameterValue
Product range (series)PowerPacT 4
Product/component typeBasic frame
Device applicationDistribution
MGP1004XFO — Ratings
ParameterValue
Rated current (In)100 A
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V
Rated impulse withstand voltage (Uimp)8 kV
Utilisation categoryCategory A
MGP1004XFO — Protection
ParameterValue
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In
Mechanical durability (cycles)50000 cycles
MGP1004XFO — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Contact position indicatorYes
Width140 mm
Height161 mm
Depth86 mm
MGP1004XFO — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to EN/IEC 60529
Pollution degree3 conforming to EN/IEC 60664-1
MGP1004XFO — Approvals
ParameterValue
StandardsBS EN 60947-2
MGP1004XFO — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity50 kA at 415 V AC 50/60 Hz

Product details

The Schneider Electric MGP1004XFO is a PowerPacT 4 basic frame — a 100 A, 4-pole (4P) molded-case circuit breaker frame rated 50 kA Icu and 50 kA Ics at 415 V AC 50/60 Hz. It ships without a trip unit, so you pair it separately for the protection curve you need. Built to BS EN 60947-2, it carries a 800 V rated insulation voltage and an 8 kV impulse withstand, with IP40 enclosure protection and IK07 impact resistance.

The 100 A rated current (In) sets the continuous load limit — size your upstream feeder and downstream bus for at least this. Utilisation category A (non-delayed) means it's designed for distribution, not motor starting — use it for cable/ busbar protection, not direct motor switching. The 4-module 35 mm width (140 mm) and 86 mm depth fit standard panelboard cutouts; backplate mounting with horizontal or vertical orientation gives layout flexibility.

Deployment context

This frame is panel-mounted in 250 A, 400 A, or 630 A panelboards — typical for commercial or industrial distribution. The Class II double-insulation rating (no earth connection needed) simplifies wiring. Altitude derating above 2000 m — if your site is above that, factor in reduced dielectric strength.

Frequently asked questions

Where can I buy MGP1004XFO and how is it quoted?

We supply MGP1004XFO to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers on the page.

What is MGP1004XFO's depth and width?

Depth is 86 mm, width is 140 mm (4 modules of 35 mm). Height is 161 mm. These dimensions fit standard panelboard cutouts.

What compliance documentation does Schneider provide for MGP1004XFO?

The frame is certified to BS EN 60947-2, carries IP40 per EN/IEC 60529, IK07 per EN/IEC 62262, and is rated Class II double insulation. Pollution degree 3 per EN/IEC 60664-1. The evidence does not list RoHS, REACH, or UL documentation specifically — check with your Schneider contact for current declarations.

MPN