Skip to main content
Schneider Electric MGP1603TX — Miniature Circuit Breakers (MCB)

Schneider Electric MGP1603TX PowerPacT 4 Circuit Breaker, 16

MPNMGP1603TX
Obsolete

Schneider Electric PowerPacT 4, circuit breaker, 3P, 160 A at 40 °C, MicroLogic 2.2 electronic trip unit, LSoI protection, panel-mounted, grey.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP1603TX — Identification
ParameterValue
Product range (series)PowerPacT 4
Product/component typeCircuit breaker
Device applicationDistribution
MGP1603TX — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)415 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V
Rated impulse withstand voltage (Uimp)8 kV
Utilisation categoryCategory A
MGP1603TX — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In
Mechanical durability (cycles)40000 cycles
MGP1603TX — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Contact position indicatorYes
Local signalling/indicationFlashing LED (green) for ready to operate LED 90 % Ir (orange) for pre-alarm indicator LED 105 % Ir (red) for overload
Width105 mm
Height161 mm
Depth86 mm
MGP1603TX — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to EN/IEC 60529
Pollution degree3 conforming to EN/IEC 60664-1
MGP1603TX — Approvals
ParameterValue
StandardsBS EN 60947-2
MGP1603TX — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz
MGP1603TX — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range63...160 A
Trip unit protection functionsLSoI

Product details

Product Overview & Key Ratings

The Schneider Electric MGP1603TX is a PowerPacT 4 panel-mounted circuit breaker, rated 160 A at 40 °C with 3 poles (3P). It carries a MicroLogic 2.2 electronic trip unit configured for LSoI protection — thermal overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). This means the breaker provides coordinated protection for distribution feeders in panelboards rated 250 A or 400/630 A, as per the product destination.

Protection & Signalling

So (short-time short-circuit) has a fixed delay, enabling zone selectivity with downstream breakers without instantaneous trip. I (instantaneous short-circuit) clears high faults immediately. There is no earth-leakage protection on this unit. Local signalling includes a flashing green LED for ready-to-operate status, an orange LED pre-alarm at 90 % Ir, and a red LED overload indication at 105 % Ir. This allows an operator to identify a pre-alarm condition before the breaker trips — useful for planned load shedding in continuous-process lines.

Mounting & Environmental Ratings

The breaker is panel-mounted (backplate) and can be installed horizontally or vertically. It occupies 3 modules of 35 mm width each, so the total width is 105 mm. Depth is 86 mm, height 161 mm. IK07 impact resistance covers low-energy impacts (0.5 J) typical of accidental tool contact. Pollution degree 3 per EN/IEC 60664-1 indicates a conductive or dry non-conductive environment; this is standard for industrial switchgear and requires appropriate creepage distances. Operating altitude is 0–2000 m without derating; above that up to 5000 m requires derating due to reduced air density affecting dielectric strength and cooling. The electrical shock protection class is II (double insulation), so no protective earth connection is needed on the breaker body.

Frequently asked questions

Where can I buy MGP1603TX and how is it quoted?

The MGP1603TX is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of MGP1603TX?

Rated 160 A at 40 °C, 3 poles, rated operational voltage 415 V AC 50/60 Hz, insulation voltage 800 V. MicroLogic 2.2 electronic trip unit with LSoI protection. Complies with BS EN 60947-2.

What compliance documentation does MGP1603TX carry?

The breaker is compliant with BS EN 60947-2, suitable for isolation per that standard, and carries Class II electrical shock protection. Pollution degree 3 per EN/IEC 60664-1. No earth-leakage protection.

MPN