Skip to main content
Schneider Electric MGP1604XE2 — Miniature Circuit Breakers (MCB)

MGP1604XE2 PowerPacT 4 Circuit Breaker, 160 A, MicroLogic 2.

MPNMGP1604XE2
Obsolete

Schneider Electric PowerPacT 4, MGP1604XE2, circuit breaker, 160 A at 40 °C, MicroLogic 2.2 electronic trip unit, 4-pole, 36 kA Icu at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP1604XE2 — Identification
ParameterValue
Product range (series)PowerPacT 4
Product/component typeCircuit breaker
Device applicationDistribution
MGP1604XE2 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V
Rated impulse withstand voltage (Uimp)8 kV
Utilisation categoryCategory A
MGP1604XE2 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In
Mechanical durability (cycles)50000 cycles
MGP1604XE2 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
MGP1604XE2 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz
MGP1604XE2 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range63...160 A
Trip unit protection functionsLSoI

Product details

The MGP1604XE2 is a panel-mounted PowerPacT 4 circuit breaker from Schneider Electric, fitted with a MicroLogic 2.2 electronic trip unit rated 160 A at 40 °C. It is a 4-pole device with a toggle control type, designed for distribution in 250 A or 400/630 A panelboards. The electronic trip unit provides LSoI protection functions (long-time, short-time, instantaneous) with an adjustable long-time pick-up range of 63...160 A and a short-time pick-up adjustable from 1.5 to 10 x Ir. The instantaneous pick-up is fixed at 2400 A.

Breaking capacity and isolation

The MGP1604XE2 delivers a rated ultimate short-circuit breaking capacity (Icu) of 36 kA at 415 V AC 50/60 Hz, with a matching service breaking capacity (Ics) of 36 kA — meaning it can clear a fault and be immediately returned to service at full rating.

It occupies 4 module spaces at 35 mm per module. The toggle control type provides manual on/off operation. No earth-leakage protection is integrated, so any ground-fault detection must be handled externally.

Frequently asked questions

Who supplies MGP1604XE2 and how is it quoted for volume purchases?

The MGP1604XE2 is sourced through independent distribution channels. It is quoted to order against an RFQ, with availability and current pricing confirmed at quote time.

What is MGP1604XE2's listed control type?

The control type is Toggle, providing manual on/off operation.

What is MGP1604XE2's listed trip unit name?

The trip unit is a MicroLogic 2.2 electronic unit with LSoI protection functions.

MPN