Skip to main content
Schneider Electric MGP2504TX — Miniature Circuit Breakers (MCB)

MGP2504TX PowerPacT 4 250A 4P Circuit Breaker, MicroLogic 2.

MPNMGP2504TX
Obsolete

Schneider Electric PowerPacT 4, MGP2504TX, 250 A at 40 °C, 4P, MicroLogic 2.2 electronic trip unit, LSoI protection, BS EN 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP2504TX — Identification
ParameterValue
Product range (series)PowerPacT 4
Product/component typeCircuit breaker
Device applicationDistribution
MGP2504TX — Ratings
ParameterValue
Rated current (In)250 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V
Rated impulse withstand voltage (Uimp)8 kV
Utilisation categoryCategory A
MGP2504TX — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
MGP2504TX — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Contact position indicatorYes
Local signalling/indicationFlashing LED (green) for ready to operate LED 90 % Ir (orange) for pre-alarm indicator LED 105 % Ir (red) for overload
Width140 mm
Height161 mm
Depth86 mm
MGP2504TX — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to EN/IEC 60529
Pollution degree3 conforming to EN/IEC 60664-1
MGP2504TX — Approvals
ParameterValue
StandardsBS EN 60947-2
MGP2504TX — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz
MGP2504TX — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range100...250 A
Trip unit protection functionsLSoI

Product details

The MGP2504TX is a Schneider Electric PowerPacT 4 panel-mounted circuit breaker rated 250 A at 40 °C with 4 poles (4P).

Deployment context

Backplate-mounted in a distribution panelboard — the MGP2504TX is sized for 250 A panelboards and also fits 400/630 A panelboard frames.

Protection and signalling detail

The electronic trip unit includes a 20-minute thermal memory before and after tripping, so the breaker remembers prior heating and responds faster on re-close. Local signalling uses a flashing green LED for ready-to-operate, an orange LED at 90 % Ir for pre-alarm, and a red LED at 105 % Ir for overload indication. The toggle control gives a clear contact position indicator. Suitability for isolation per BS EN 60947-2 means it can be used as a disconnecting means.

Durability and environmental range

Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V In/2, or 10,000 cycles at 440 V In. Operating altitude from 0 to 2000 m without derating, 2000 to 5000 m with derating. IK07 impact resistance and Class II electrical shock protection. No earth-leakage protection and no zone selective interlocking (ZSI) on this variant.

Frequently asked questions

How do I get current pricing and availability for MGP2504TX?

The MGP2504TX is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is MGP2504TX's rated current and voltage?

The MGP2504TX is rated 250 A at 40 °C with a rated operational voltage of 415 V AC 50/60 Hz and an insulation voltage of 800 V.

What protection functions does the MicroLogic 2.2 trip unit provide?

The MicroLogic 2.2 provides LSoI protection: L for thermal overload, So for short-time short-circuit with fixed delay, and I for instantaneous short-circuit.

What compliance documentation is available for MGP2504TX?

The MGP2504TX complies with BS EN 60947-2 for circuit-breaker performance and isolation suitability, and carries IP40 and IK07 protection ratings per EN/IEC 60529 and EN/IEC 62262. Pollution degree 3 per EN/IEC 60664-1. Specific RoHS/REACH/UL documentation is confirmed at quote time.

MPN
MGP2504TX