Specifications

MGP4004X key specifications
ParameterValue
Control typeToggle
Protection typeL : for overload protection (thermal) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Range of productPowerPacT 4
Product or component typeCircuit breaker
Voltage800 V
[Ue] rated operational voltage415 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Current400 A at 40 °C
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz
Poles description4P
Utilisation categoryCategory A

All specifications

MGP4004X additional specifications
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
Circuit breaker mounting modePanel-mounted
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In
Mechanical durability15000 cycles
StandardsBS EN 60947-2
Trip unit nameMicroLogic 2.3
Trip unit rating400 A at 40 °C
Number of modules6 module(s)35 mm
Device applicationDistribution
Product destination400/630 A panelboard
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Trip unit protection functionsLSoI
Thermal protection adjustment range160...400 A
MPN
MGP4004X