Skip to main content
Schneider Electric NTSAMI0210K

Schneider Electric NTSAMI0210K

MPNNTSAMI0210K
Active

Analog Input Module + Base, 2 Isolated In, Current, Voltage, 2/3/4 wires, Loop Power, Modicon Edge I/O NTS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NTSAMI0210K key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc)
Analogue input typeCurrent +/- 20 mA Current 0...20 mA Current 4...20 mA Voltage +/- 10 V Voltage 0...10 V Voltage +/- 5 V Voltage 0...5 V Voltage 1...5 V
Input protection typeOver current / miswiring protection per channel for current input Over voltage / miswiring protection per channel for voltage input
Product or component typeAnalog input module
Rated operational voltage limits20.4...28.8 V DC
Typical current consumption36 mA 24 V DC on the Bus current 38.4 mA 24 V DC on the internal field current minimum 246.1 mA 24 V DC on the internal field current maximum
Sensor power supply19.2...30 V DC sensor power supply 24 V DC Loop power
Power dissipation in1.3 W maximum at 24 V DC
Sensor power supply protectionOver current protection per channel Short circuit protection on loop power supply per channel
Isolation between field power and bus1500 V AC

All specifications

NTSAMI0210K additional specifications
ParameterValue
IP degree of protectionIP20
Mounting supportTop hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715
Maximum cable distance between devicesShielded cable Shielded cable <3280.8 ft (1000 m) current input
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth3.1 in (80 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
LSB value0.31 mV, +/- 10 V 0.31 mV, 0...10 V 0.16 mV, +/- 5 V 0.16 mV, 0...5 V 0.13 mV, 1...5 V 0.61 µA, +/- 20 mA 0.61 µA, 0...2 mA 0.49 µA, 4...20 mA
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Non-linearity<= 0.01 % FS voltage/current
HART toleranceYes
Operating modeSynchronous/Isochronous/Asynchronous
Input impedance> 10 MOhm in voltage mode 250 Ohm + internal current protector 10 Ohm typical
Kit compositionNTSAMI0210 module NTSXBA0100H base
Input diagnosticUnderflow error per channel Overflow error per channel Broken wire error per channel Hardware error per channel Calibration error per channel Loop power supply error per channel
Local signalling1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR)
Input wiring mode2, 3 or 4 wires
Measurement error<= 0.1 % FS - 20...60 °C
Sampling duration0.499 ms
Temperature drift± 0.001 % FS/ °C
Device applicationIndustrial Application
Mandatory accessoryNTSXTB12_0_H terminal block
Analogue input number2
Common mode rejection90 dB
Hot swapping fallbackYes
Analogue input resolution15 bits + sign
Isolation between channels530 V AC
Environmental characteristicGas resistant C3 and G2
Permitted overload on inputs30 V maximum voltage 30 V at 50 mA maximum current
Isolation between channels and bus1500 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-4...140 °F (-20...60 °C)
Isolation between channels and field pwrNo for module sensor power supply 1000 Vac for module loop power supply
MPN
NTSAMI0210K