Specifications

NTSAMI0400K key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc)
Analogue input typeCurrent +/- 20 mA Current 0...20 mA Current 4...20 mA Voltage +/- 10 V Voltage 0...10 V Voltage +/- 5 V Voltage 0...5 V Voltage 1...5 V
Input protection typeOver current / miswiring protection per channel for current input Over voltage / miswiring protection per channel for voltage input
Product or component typeAnalog input module kit
Rated operational voltage limits20.4...28.8 V DC
Typical current consumption31.7 mA 24 V DC on the Bus current 19.2 mA 24 V DC on the internal field current minimum 23 mA 24 V DC on the internal field current maximum
Power dissipation in1.6 W maximum at 24 V DC
Isolation between field power and bus1500 V AC
IP degree of protectionIP20
Mounting supportTop hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715

All specifications

NTSAMI0400K additional specifications
ParameterValue
Maximum cable distance between devicesShielded cable Shielded cable <3280.8 ft (1000 m) current input
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth3.1 in (80 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
LSB value0.31 mV, +/- 10 V 0.31 mV, 0...10 V 0.16 mV, +/- 5 V 0.16 mV, 0...5 V 0.13 mV, 1...5 V 0.61 µA, +/- 20 mA 0.61 µA, 0...2 mA 0.49 µA, 4...20 mA
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Non-linearity<= 0.01 % FS voltage/current
Operating modeIsochronous/Asynchronous
Input impedance> 10 MOhm in voltage mode 100 Ohm + internal current protector 10 Ohm typical
Kit compositionNTSAMI0400 module NTSXBA0100H base
Input diagnosticUnderflow error per channel Overflow error per channel Broken wire error per channel Hardware error per channel
Local signalling1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR)
Input wiring mode2 wires
Measurement error<= 0.5 % FS - 20...60 °C
Sampling duration0.980 ms per module
Temperature drift± 0.0057 % FS/ °C
Device applicationIndustrial Application
Mandatory accessoryNTSXTB12_0_H terminal block
Analogue input number4
Common mode rejection90 dB
Hot swapping fallbackYes
Analogue input resolution15 bits + sign
Permitted overload on inputs30 V maximum voltage 30 V at 50 mA maximum current
Isolation between channels and bus1500 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-4...140 °F (-20...60 °C)
Isolation between channels and field pwrNo