Schneider Electric NTSAMI0420K
MPNNTSAMI0420K
Active
Analog Input Module + Base, 4 Differential In, Current, Voltage, 2 Wires, Modicon Edge I/O NTS
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Type of cable | Shielded cable |
| Range of product | Modicon Edge I/O NTS |
| Power supply type | Bus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc) |
| Analogue input type | Current +/- 20 mA Current 0...20 mA Current 4...20 mA Voltage +/- 10 V Voltage 0...10 V Voltage +/- 5 V Voltage 0...5 V Voltage 1...5 V |
| Input protection type | Over current / miswiring protection per channel for current input Over voltage / miswiring protection per channel for voltage input |
| Product or component type | Analog input module kit |
| Rated operational voltage limits | 20.4...28.8 V DC |
| Typical current consumption | 31.7 mA 24 V DC on the Bus current 27.6 mA 24 V DC on the internal field current minimum 33.1 mA 24 V DC on the internal field current maximum |
| Power dissipation in | 1.8 W maximum at 24 V DC |
| Isolation between field power and bus | 1500 V AC |
| IP degree of protection | IP20 |
| Mounting support | Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 |
All specifications
| Parameter | Value |
|---|---|
| Maximum cable distance between devices | Shielded cable Shielded cable <3280.8 ft (1000 m) current input |
| Pollution degree | 2 |
| Shock resistance | 15 g 11 ms with and without accessory) |
| Relative humidity | 5...95 % without condensation |
| Operating altitude | 0...6561.68 ft (0...2000 m) 2000...5000 m with derating |
| Vibration resistance | 1 g without accessory 2 g with accessory |
| Depth | 3.1 in (80 mm) |
| Width | 0.6 in (15 mm) |
| Height | 3.9 in (100 mm) |
| Housing colour | Grey |
| Product weight | 0.161 lb(US) (0.073 kg) |
| Standards | EN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5 |
| Marking | CE UKCA CULus RCM |
| Category | US1PC3318214 |
| LSB value | 0.31 mV, +/- 10 V 0.31 mV, 0...10 V 0.16 mV, +/- 5 V 0.16 mV, 0...5 V 0.13 mV, 1...5 V 0.61 µA, +/- 20 mA 0.61 µA, 0...2 mA 0.49 µA, 4...20 mA |
| Directives | 2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU |
| Non-linearity | <= 0.01 % FS voltage/current |
| Operating mode | Isochronous/Asynchronous |
| Input impedance | > 10 MOhm in voltage mode 100 Ohm + internal current protector 10 Ohm typical |
| Kit composition | NTSAMI0420 module NTSXBA0100H base |
| Input diagnostic | Underflow error per channel Overflow error per channel Broken wire error per channel Hardware error per channel |
| Local signalling | 1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR) |
| Input wiring mode | 2 wires |
| Measurement error | <= 0.5 % FS - 20...60 °C |
| Sampling duration | 0.723 ms per module |
| Temperature drift | ± 0.0057 % FS/ °C |
| Device application | Industrial Application |
| Mandatory accessory | NTSXTB12_0_H terminal block |
| Analogue input number | 4 |
| Common mode rejection | 70 dB |
| Hot swapping fallback | Yes |
| Analogue input resolution | 15 bits + sign |
| Environmental characteristic | Gas resistant C3 and G2 |
| Permitted overload on inputs | 30 V maximum voltage 30 V at 50 mA maximum current |
| Isolation between channels and bus | 1500 V AC |
| Ambient air temperature for storage | -40...185 °F (-40...85 °C) |
| Ambient air temperature for operation | -4...140 °F (-20...60 °C) |
| Isolation between channels and field pwr | 1000 V AC |