Skip to main content
Schneider Electric NTSART0214HK

Schneider Electric NTSART0214HK

MPNNTSART0214HK
Active

Temperature Input Module + Base, 2 Isolated In, RTD, ThC, mV, 2/3/4 wires, Hardened, Modicon Edge I/O NTS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NTSART0214HK key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc)
Analogue input typeVoltage +/- 40 mV Voltage +/- 80 mV Voltage +/- 160 mV Voltage +/- 320 mV Voltage +/- 640 mV Voltage +/- 1.28 V RTD Ni 100/Ni 1000 RTD Pt 100/Pt 1000
Input protection typeOver voltage protection
Product or component typeTemperature input module kit
Rated operational voltage limits20.4...28.8 V
Typical current consumption36 mA 24 V DC on the Bus current 16.8 mA 24 V DC on the internal field current minimum 20.2 mA 24 V DC on the internal field current maximum
Power dissipation in1.4 W maximum at 24 V DC
Isolation between field power and bus1500 V AC
IP degree of protectionIP20
Mounting supportTop hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715

All specifications

NTSART0214HK additional specifications
ParameterValue
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth3.1 in (80 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
Product weight0.161 lb(US) (0.073 kg)
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Operating modeAsynchronous
Kit compositionNTSART0214H module NTSXBA0100H base
Local signalling1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR)
Measurement error<= 0.05 % FS 25 °C
Device applicationIndustrial Application
Mandatory accessoryNTSXTB12_0_H terminal block
Analogue input number2
Common mode rejection100 dB
Hot swapping fallbackYes
Isolation between channels530 V AC
Environmental characteristicGas resistant CX & GX combined Salt spray resistant
Isolation between channels and bus1500 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-4...140 °F (-20...60 °C)
Isolation between channels and field pwr1000 V AC
MPN
NTSART0214HK