Schneider Electric NTSART0214
MPNNTSART0214
Active
Temperature Input Module, 2 Isolated In, RTD, ThC, mV, 2/3/4 Wires, Modicon Edge I/O NTS
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Type of cable | Shielded cable |
| Range of product | Modicon Edge I/O NTS |
| Power supply type | Bus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc) |
| Analogue input type | Voltage +/- 40 mV Voltage +/- 80 mV Voltage +/- 160 mV Voltage +/- 320 mV Voltage +/- 640 mV Voltage +/- 1.28 V RTD Ni 100/Ni 1000 RTD Pt 100/Pt 1000 RTD Cu 10/50/100 RTD JPt 100/1000 RTD high precision Cu50/100, Ni100/1000, Pt100/1000 Resistor 150/300/600/2000/4500 Ohm Thermocouple type J/K/R/S/B/T/N/E/C/L/U |
| Input protection type | Over voltage protection |
| Product or component type | Temperature input module |
| Rated operational voltage limits | 20.4...28.8 V |
| Typical current consumption | 36 mA 24 V DC on the Bus current 16.8 mA 24 V DC on the internal field current minimum 20.2 mA 24 V DC on the internal field current maximum |
| Power dissipation in | 1.4 W maximum at 24 V DC |
| Isolation between field power and bus | 1500 V AC |
| IP degree of protection | IP20 |
| Mounting support | base |
All specifications
| Parameter | Value |
|---|---|
| Maximum cable distance between devices | Shielded cable Shielded cable <656.2 ft (200 m) |
| Pollution degree | 2 |
| Shock resistance | 15 g 11 ms with and without accessory) |
| Relative humidity | 5...95 % without condensation |
| Operating altitude | 0...6561.68 ft (0...2000 m) 2000...5000 m with derating |
| Vibration resistance | 1 g without accessory 2 g with accessory |
| Depth | 2.7 in (69 mm) |
| Width | 0.6 in (15 mm) |
| Height | 3.9 in (100 mm) |
| Housing colour | Grey |
| Product weight | 0.106 lb(US) (0.048 kg) |
| Standards | EN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5 |
| Marking | CE UKCA CULus RCM |
| Category | US1PC3318214 |
| Directives | 2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU |
| Non-linearity | <= 0.01 % FS thermocouple/RTD input |
| Operating mode | Asynchronous |
| Input impedance | 1 MOhm typical |
| Input diagnostic | Underflow error per channel Overflow error per channel Broken wire error per channel Hardware error per channel Calibration error per channel CJC error per channel Internal field power supply error per channel |
| Local signalling | 1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR) |
| Input wiring mode | 2, 3 or 4 wires for RTD and resistance inputs 2-wire for thermocouple and voltage inputs |
| Measurement error | <= 0.09 % FS - 20...60 °C |
| Sampling duration | 60 ms at 50Hz rejection per channel 60 ms at 60Hz rejection per channel |
| Temperature drift | +/- 0.003 %/°C |
| Device application | Industrial Application |
| Mandatory accessory | NTSXBA0100H base NTSXTB12_0_H terminal block |
| Analogue input number | 2 |
| Common mode rejection | 100 dB |
| Hot swapping fallback | Yes |
| Analogue input resolution | 16 bits with overflow |
| Isolation between channels | 530 V AC |
| Environmental characteristic | Gas resistant CX & GX combined Salt spray resistant |
| Permitted overload on inputs | +/- 2.4 % over voltage range |
| Isolation between channels and bus | 1500 V AC |
| Ambient air temperature for storage | -40...185 °F (-40...85 °C) |
| Ambient air temperature for operation | -4...140 °F (-20...60 °C) |
| Isolation between channels and field pwr | 1000 V AC |
MPN