Skip to main content
Schneider Electric NTSDAI0215HK

Schneider Electric NTSDAI0215HK

MPNNTSDAI0215HK
Active

Discrete Input Module + Base, 2 Isolated In, 100V to 240V AC, Sink, 1/2/3 Wires, Hardened, Modicon Edge I/O NTS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NTSDAI0215HK key specifications
ParameterValue
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from external power supply (100...240 Vac)
Product or component typeDiscrete input module kit
Discrete input voltage100...240 V AC
Voltage state 0 guaranteed= 2 mA
Voltage state 1 guaranteed>= 79 V
Rated operational voltage limits85...264 V AC 47...63 Hz
Discrete input current3.6 mA at 120 V AC 50 Hz 7.1 mA at 230 V AC 50 Hz
Typical current consumption26.4 mA 24 V DC on the Bus current 0 mA 24 V DC on the internal field current
Power dissipation in1.17 W maximum at 24 V DC
Discrete input frequency47...63 Hz
IP degree of protectionIP20

All specifications

NTSDAI0215HK additional specifications
ParameterValue
Electrical connectionScrew/spring terminal block
Response time on input5.8 ms (on to off)
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth3.1 in (80 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
Product weight0.161 lb(US) (0.073 kg)
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5, interface type 1 and type 2 EN/IEC 61850-3, location G EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Operating modeAsynchronous
Input filtering5.8...20 ms configurable in 0.1 ms step
Kit compositionNTSDAI0215H module NTSXBA0100H base
Input diagnosticExternal power supply error per channel Broken wire error per channel
Local signalling1 LED (green) for module operating (RUN) 1 LED per channel (green) for channel diagnostic 1 LED (red) for module error (ERR)
Input wiring mode1, 2 or 3 wires
Device applicationIndustrial application in severe environment
Mandatory accessoryNTSXTB12_1_H terminal block
Protective treatmentConformal coating
Discrete input number2
Hot swapping fallbackYes
Group of input channels2 groups of 1 channel
Isolation between channels1780 V AC
Discrete input compatibility2 type 1 conforming to IEC 61131-2
Environmental characteristicGas resistant CX & GX combined Salt spray resistant
Isolation between channels and bus3000 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-40...158 °F (-40...70 °C)
Isolation between channels and ground3000 V AC
MPN
NTSDAI0215HK