Skip to main content
Schneider Electric NTSDAO0205K

Schneider Electric NTSDAO0205K

MPNNTSDAO0205K
Active

Discrete Output Module + Base, 2 Out, 1A, 100V to 240V AC, 1/2/3 Wires, Modicon Edge I/O NTS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NTSDAO0205K key specifications
ParameterValue
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from external power supply (100...240 Vac)
Output protection typeRC snubber suppression per channel
Product or component typeDiscrete output module kit
Maximum voltage drop<1.55 V AC
Discrete output voltage80...264 V AC
Rated operational voltage limits85...264 V AC 47...63 Hz
Maximum leakage current2.5 mA 240 V AC 2 mA 120 V AC
Typical current consumption30 mA 24 V DC on the Bus current 0 mA 24 V DC on the internal field current
Power dissipation in2.36 W maximum at 24 V DC
Discrete output frequency47...63 Hz
IP degree of protectionIP20

All specifications

NTSDAO0205K additional specifications
ParameterValue
Mounting supportTop hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715
Electrical connectionScrew/spring terminal block
Response time on output0.5 ms turn-on 0.5 ms turn-off
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth3.1 in (80 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
Product weight0.161 lb(US) (0.073 kg)
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5, interface type 1 and type 2 EN/IEC 61850-3, location G EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Operating modeAsynchronous
Kit compositionNTSDAO0205 module NTSXBA0100H base
Local signalling1 LED (green) for module operating (RUN) 1 LED per channel (green) for channel diagnostic 1 LED (red) for module error (ERR)
Output diagnosticExternal power supply error per channel
Device applicationIndustrial Application
Output wiring mode1, 2 or 3 wires
Mandatory accessoryNTSXTB12_1_H terminal block
Hot swapping fallbackYes
Discrete output number2 triac
Paralleling of outputsYes for logic links Yes for redundant control of load
Group of output channels1 group
Environmental characteristicGas resistant C3 and G2
Isolation between channels and bus3000 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-4...140 °F (-20...60 °C)
Isolation between channels and ground3000 V AC
MPN