Specifications

PP40251L1 key specifications
ParameterValue
Control typeToggle
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Range of productPowerPacT 4
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Fixed
Voltage750 V
[Ue] rated operational voltage230 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Current25 A at 40 °C
[Ics] rated service short-circuit breaking capacity25 kA at 230 V AC 50/60 Hz

All specifications

PP40251L1 additional specifications
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 230 V AC 50/60 Hz
Poles description1P
Phase connectionL1
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to EN/IEC 62262
IP degree of protectionIP40 conforming to EN/IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical
Circuit breaker mounting modePanel-mounted
Pollution degree3 conforming to EN/IEC 60664-1
Operating altitude0...2000 m without derating 2000...5000 m with derating
Electrical shock protection classClass II
ColorGrey
Electrical durability20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability20000 cycles
StandardsBS EN 60947-2
Trip unit nameTM-D
Trip unit rating25 A at 40 °C
Number of modules1 module(s)35 mm
Safety categoryN
Device applicationDistribution
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Contact position indicatorYes
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Ir] long-time protection pick-up adjustment range1 x In
[Ii] instantaneous protection pick-up adjustment range300 A
MPN