Specifications

PP40403X key specifications
ParameterValue
Control typeToggle
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Range of productPowerPacT 4
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Fixed
Voltage800 V
[Ue] rated operational voltage415 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Current40 A at 40 °C
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz

All specifications

PP40403X additional specifications
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz
Power dissipation per pole5.47 W
Poles description3P
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to EN/IEC 62262
IP degree of protectionIP40 conforming to EN/IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical
Circuit breaker mounting modePanel-mounted
Pollution degree3 conforming to EN/IEC 60664-1
Operating altitude0...2000 m without derating 2000...5000 m with derating
Electrical shock protection classClass II
Depth86 mm
Width105 mm
ColorGrey
Height161 mm
Electrical durability50000 cycles at 440 V In/2 30000 cycles at 440 V In
Mechanical durability50000 cycles
StandardsBS EN 60947-2
Trip unit nameTM-D
Trip unit rating40 A at 40 °C
Number of modules3 module(s)35 mm
Safety categoryF
Device applicationDistribution
Product destination250 A panelboard 400/630 A panelboard
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Contact position indicatorYes
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range500 A
MPN