Specifications

PP44003X key specifications
ParameterValue
Control typeToggle
Protection typeL : for overload protection (thermal) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Range of productPowerPacT 4
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Fixed
Voltage800 V
[Ue] rated operational voltage415 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV

All specifications

PP44003X additional specifications
ParameterValue
Current400 A at 40 °C
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 415 V AC 50/60 Hz
Power dissipation per pole19.2 W
Poles description3P
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to EN/IEC 62262
IP degree of protectionIP40 conforming to EN/IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical
Circuit breaker mounting modePanel-mounted
Pollution degree3 conforming to EN/IEC 60664-1
Operating altitude0...2000 m without derating 2000...5000 m with derating
Electrical shock protection classClass II
Depth110 mm
Width140 mm
ColorGrey
Height255 mm
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In
Mechanical durability15000 cycles
StandardsBS EN 60947-2
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 2.3
Local signallingFlashing LED (green) for ready to operate LED 90 % Ir (orange) for pre-alarm indicator LED 105 % Ir (red) for overload
Trip unit rating400 A at 40 °C
Number of modules4 module(s)35 mm
Safety categoryF
Device applicationDistribution
Product destination400/630 A panelboard
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60947-2
Contact position indicatorYes
Trip unit protection functionsLSoI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir
[Ir] long-time protection pick-up adjustment range160...400 A
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range4800 A
MPN