Schneider Electric REL10214
MPNREL10214
Obsolete
P116 withdrawable solution - In 5A - Ion 5A 0.01-8Ion - Vx 60-240VAC/60-250VDC
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product range | MiCOM P11x |
| Device short name | P116 |
| Parameter | Value |
|---|---|
| Display type | LCD display: 2 lines of 16 characters ASCII (European characters) and 9 key |
| Metering type | Phase currents |
| Mounting mode | Flush-mounted |
| Device mounting | Flush |
| Protection type | ANSI 79 : recloser ANSI 86 : lockout ANSI 49RMS : thermal overload protection ANSI 37 : phase undercurrent ANSI 50N/51N : earth fault ANSI 50BF : breaker failure ANSI 50/51 : phase overcurrent ANSI 46 : negative sequence/unbalance ANSI 46BC : broken conductor |
| Auxiliary supply | 60...240 V AC 60...250 V DC |
| Relay application | Feeder |
| Type of measurement | Current |
| Earth current inputs | 5 A 0.01...8 Ion 5 A 0.1...40 In |
| Protocol | Modbus RTU by RS485 in rear IEC 60870-5-103 by USB in front |
| Input output max capacity | 6 inputs + 7 outputs |
| Supply voltage | 90...240 V AC 71...265 V 60...250 V DC 48...300 V |
| Communication port support | RS485 USB |
| Communication port protocol | IEC 60870-5-103 Modbus RTU |
| Control and monitoring type | Latching/acknowledgement Switching of groups of settings |
| Network and machine diagnosis type | Fault recording Event recording |
MPN
REL10214