Skip to main content
Schneider Electric REL15008C — Unclassified

Schneider Electric REL15008C

MPNREL15008C
Active

protection relay PowerLogic P1F 24-60V 3CT 1Io: 0.05-12IN 4DI-4DO RS485 USB

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

REL15008C key specifications
ParameterValue
Display typeGraphic display terminal
Range of productPowerLogic
Product or component typeProtection relay
Switchgear diagnosis typeTrip circuit supervision ANSI code: TCS
Type of temperature module connection1 twisted shielded pair
Power supply24...60 V AC 24...60 V DC
Maximum power consumption in13.5 W AC 4 W DC
IP degree of protectionIP54 conforming to IEC 60529
Communication ports1 RS485 on rear 1 USB type mini B on front
Communication protocolsCEI 60870-5-103 Modbus RTU
Communication compatibilityIEC 60870-5-103 Modbus RTU
Mounting modeFlush-mounted

All specifications

REL15008C additional specifications
ParameterValue
Device mountingFlush
Mounting supportFixing kit
Device connectionSerial port 1 shielded twisted pair
Connections - terminalsSnap-on fixed
Relative humidity0...93 % at 40 °C, 21 days 0...93 % at 60 °C, 10 days 93 % at 25...55 °C, 6 cycles, 12 + 12 hours
DepthEmbedded : 108 mm Total : 119 mm
WidthEmbedded: 101.5 mm Total: 116.5 mm
HeightEmbedded: 101.5 mm Total: 116.5 mm
StandardsEN 60255-26:2009 EN 60255-1:2010 EN 60255-27:2005
Directives2006/95/EC - low voltage directive 2004/108/EC - electromagnetic compatibility
CybersecurityPassword protection
Number of key9
Software nameESetup Easergy Pro: device setup
Local signalling6 x LED red/orange programmable 1 x LED red relay trip indicator 1 x LED green watchdog
Logs and recordsEvent recording Trip context information
Measuring inputs: 1/5 A CT phase current 4
Control functionsLocal/remote control I/O push-button Digital Using serial port
Product referenceP1
Relay applicationFeeder
Arc flash protectionNo
Monitoring functionsTrip circuit supervision 74 Relay self-monitoring
Protection functionsBreaker failure 50BF Phase overcurrent 50/51 Earth fault overcurrent 50N/51N Lockout relay 86 Thermal overload protection 49 Cold load pick-up Switch ON to fault (SOTF)
Measurement functionsCurrent 3-phase Current RMS Current peak Frequency Temperature overload
Mechanical robustnessSeismic tests: 2 Gn horizontal, 1 Gn vertical conforming to EN 60255-21-3 Shocks (level: class 1) : 5 Gn for 11 ms conforming to EN 60255-21-2 Shocks withstand (level: class 1) : 10 Gn for 16 ms conforming to EN 60255-21-2 Bumps (level: class 1) : 15 Gn for 11 ms conforming to EN 60255-21-2 Vibrations (level: class 1) : 1 Gn, 10...150 Hz, 1 cycle conforming to EN 60255-21-1
Electromagnetic compatibilityElectromagnetic immunity level 3 conforming to EN 61000-4-2/3/4/5/6/8
Number of digital inputs4
Number of digital outputs4 DO 1 watchdog
Ambient air temperature for storage-30...70 °C
Ambient air temperature for operation-25...60 °C -30...70 °C ( 16 h )
MPN
REL15008C