Schneider Electric RHK412BEA76
MPNRHK412BEA76
Obsolete
Plug in relay, Zelio Relay with suppressor, RHK, latching, 4 C/O, 27 V DC, 5 A
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Manual control |
| Range of product | Harmony Relay |
| Product or component type | Plug-in relay |
| Contacts type and composition | 4 C/O |
| Maximum voltage drop | <100 V for 3 A at 24 V |
| Drop-out voltage threshold | 0.1...0.3 Uc |
| Coil voltage | 27 V DC |
| Voltage | 250 V |
| Control circuit voltage limits | 0.8...1.1 Uc IEC 60255 |
| [Ithe] conventional enclosed thermal current | 5 A 104 °F (40 °C) |
| Terminals description ISO n°1 | (11-12-14)OC |
| Shock resistance | 30 gn 11 ms NF C 20-608 |
All specifications
| Parameter | Value |
|---|---|
| Vibration resistance | 6 gn (f= 10...55 Hz) conforming to IEC 60068-2-6 6 gn (f= 10...55 Hz) conforming to NF C 20-616 |
| CAD overall depth | 3.5 in (90 mm) |
| CAD overall width | 1.3 in (33 mm) |
| CAD overall height | 1.7 in (43 mm) |
| Mechanical durability | 10000000 cycles |
| Standards | NF C 45-250 VDE 0435 BS 4794 IEC 255 |
| Category | 18403-WORLD SERVICE PARTS(ENVELOPES) |
| Status LED | Without |
| Test levels | Level A group mounting |
| Time constant | 12 ms open 15 ms closed |
| Operating time | 10...14 ms between energisation of trip coil and closing of NC contact 68 °F (20 °C) 12...22 ms between energisation of coil and closing of NO contact 68 °F (20 °C) 1...4 ms energisation/de-energisation 1.2...4 ms de-energisation/energisation |
| Contact operation | Latching Standard |
| Device short name | RHK |
| Average resistance | 30 mOhm 68 °F (20 °C) |
| Compatibility code | RHK |
| Operating position | Any position |
| Contact bounce time | <= 10 ms |
| Dielectric strength | 2500 V |
| Protective treatment | TC |
| Maximum operating rate | 2 cyc/mn |
| Minimum pulse duration | 50 ms |
| Average coil consumption | 1.6 W 68 °F (20 °C) coil 1 2.9 W 68 °F (20 °C) coil 2 |
| Minimum switching capacity | 150 mVA 10 mA 150 mVA, 1 V |
| Coil interference suppression | With |
| Ambient air temperature for storage | -40...158 °F (-40...70 °C) |
| Ambient air temperature for operation | 23...104 °F (-5...40 °C) IEC 60255 |
MPN