RM4JA31M key specifications
ParameterValue
TypeCurrent measurement relay
Time delay typeAdjustable 0.05...30 s
Range of productHarmony Relay
Product or component typeIndustrial measurement and control relays
Contacts type and composition2 C/O
Switching voltage250 V AC
Dielectric test voltage2.5 kV
Maximum switching voltage440 V AC
Operating voltage tolerance0.85...1.1 Uc
[Ie] rated operational current2 A 24 V DC-13 158 °F (70 °C) IEC 60947-5-1/1991 2 A 24 V DC-13 158 °F (70 °C) VDE 0660 3 A 115 V AC-15 158 °F (70 °C) IEC 60947-5-1/1991 3 A 115 V AC-15 158 °F (70 °C) VDE 0660 3 A 24 V AC-15 158 °F (70 °C) IEC 60947-5-1/1991 3 A 24 V AC-15 158 °F (70 °C) VDE 0660 3 A 250 V AC-15 158 °F (70 °C) IEC 60947-5-1/1991 3 A 250 V AC-15 158 °F (70 °C) VDE 0660 0.1 A 250 V DC-13 158 °F (70 °C) IEC 60947-5-1/1991 0.1 A 250 V DC-13 158 °F (70 °C) VDE 0660 0.3 A 115 V DC-13 158 °F (70 °C) IEC 60947-5-1/1991 0.3 A 115 V DC-13 158 °F (70 °C) VDE 0660
[Ith] conventional free air thermal current8 A
Maximum power consumption in3.4 VA AC

All specifications

RM4JA31M additional specifications
ParameterValue
IP degree of protectionIP20 IEC 60529 terminals) IP50 IEC 60529 casing)
Number of cables2
Connections - terminalsScrew terminals, 2 x 1.5 mm²flexible with cable end Screw terminals, 2 x 2.5 mm²flexible without cable end
Terminals description ISO n°1(C-B1-B2-B3)CO (25-26-28)OC (A1-A2)CO (15-16-18)OC
Pollution degree3 IEC 60664-1
Shock resistance15 gn 11 ms IEC 60255-21-1
Relative humidity15...85 % IEC 60721-3-3
Non-dissipating shock wave4.8 kV
Protection against electric shocks2 kV level 3 IEC 61000-4-5
Depth3.1 in (80 mm)
Width0.9 in (23 mm)
Height3.07 in (78 mm)
Contacts material90/10 silver nickel contacts
Mechanical durability30000000 cycles
StandardsIEC 60255-6
Category22376-RELAYS-MEASUREMENT(RM4)
Relay nameRM4J
9 mm pitches2.5
Output contacts2 C/O
Measurement range0.3...30 mA current DC 10...100 mA current DC 100...1000 mA current DC 0.3...30 mA current AC 10...100 mA current AC 100...1000 mA current AC
Tightening torque5.3...9.7 lbf.in (0.6...1.1 N.m)
Operating positionAny position without derating
Output relay stateTripped if V measured > V set Tripped if A measured > A set
Maximum measuring cycle80 ms
Switching capacity in10 mA 12 V
Internal input resistance1 Ohm 10 Ohm 33 Ohm
Switching threshold drift0.1 Uc
Relay monitored parametersOvercurrent or undercurrent detection
Environmental characteristic3K3
Electromagnetic compatibilityElectrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Resistance to fast transients2 kV IEC 61000-4-4 level 3
Disturbance radiated (conducted)CISPR 22 - class A CISPR 11 group 1 - class A
Permissible continuous overload0.05 A 1.5 A 0.15 A
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Permissible non repetitive overload5 A 0.2 A 0.5 A
Resistance to electromagnetic fields9.1 V/m (10 V/m) IEC 61000-4-3 level 3
Ambient air temperature for operation-4...149 °F (-20...65 °C)
Resistance to electrostatic discharge6 kV contact IEC 61000-4-2 level 3 8 kV air IEC 61000-4-2 level 3
Setting accuracy of the switching threshold+/-5 %
MPN