Skip to main content
Schneider Electric RM4LA32F

Schneider Electric RM4LA32F

MPNRM4LA32F
Obsolete

LIQUID LEVEL RELAY 300V 5A RM4|LIQUID LEVEL RELAY 300V 5A RM4

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

RM4LA32F key specifications
ParameterValue
TypeLiquid level control relay
Range of productHarmony Relay
Product or component typeIndustrial measurement and control relays
Contacts type and composition2 C/O
Switching voltage250 V AC
Dielectric test voltage2.5 kV
Maximum electrode voltage24 V AC
Maximum switching voltage440 V AC
Operating voltage tolerance0.85...1.1 Uc
Voltage500 V IEC
Maximum electrode current1 mA
[Ie] rated operational current2 A 158 °F (70 °C) 24 V DC-13 IEC 60947-5-1/1991 2 A 158 °F (70 °C) 24 V DC-13 VDE 0660 3 A 158 °F (70 °C) 115 V AC-15 IEC 60947-5-1/1991 3 A 158 °F (70 °C) 115 V AC-15 VDE 0660 3 A 158 °F (70 °C) 24 V AC-15 IEC 60947-5-1/1991 3 A 158 °F (70 °C) 24 V AC-15 VDE 0660 3 A 158 °F (70 °C) 250 V AC-15 IEC 60947-5-1/1991 3 A 158 °F (70 °C) 250 V AC-15 VDE 0660 0.1 A 158 °F (70 °C) 250 V DC-13 IEC 60947-5-1/1991 0.1 A 158 °F (70 °C) 250 V DC-13 VDE 0660 0.3 A 158 °F (70 °C) 115 V DC-13 IEC 60947-5-1/1991 0.3 A 158 °F (70 °C) 115 V DC-13 VDE 0660

All specifications

RM4LA32F additional specifications
ParameterValue
[Ith] conventional free air thermal current8 A
Power consumption2.7 VA AC
IP degree of protectionIP20 IEC 60529 terminals) IP50 IEC 60529 casing)
Number of cables2
Maximum cable capacity0 mF
Connections - terminalsScrew terminals, 2 x 1.5 mm²flexible with cable end Screw terminals, 2 x 2.5 mm²flexible without cable end
Terminals description ISO n°1(A1-A2)CO (15-16-18)OC (25-26-28)OC (B1-B2-B3)CO
Pollution degree3 IEC 60664-1
Relative humidity15...85 % 3K3 IEC 60721-3-3
Protection against electric shocks2 kV level 3 IEC 61000-4-5
Width0.9 in (22.5 mm)
Contacts material90/10 silver nickel contacts
Mechanical durability30000000 cycles
StandardsIEC 60255-6
MarkingCE : LVD 73/23/EEC CE : EMC 89/336/EEC
Category22376-RELAYS-MEASUREMENT(RM4)
Relay nameRM4-L
Time delayAdjustable 0.1...10 s
9 mm pitches2.5
Output contacts2 C/O
Sensitivity scale0.25...5 kOhm LS (Low Sensitivity) 2.5...50 kOhm St (Standard Sensitivity) 25...500 kOhm HS (High Sensitivity)
Tightening torque5.3...9.7 lbf.in (0.6...1.1 N.m)
Operating positionAny position without derating
Output relay stateAccording to chosen function
Overvoltage categoryIII conforming to IEC 60664-1
Switching capacity in10 mA 12 V
Relay monitored parametersDetection by resistive probes
Supply disconnection value> 0.1 Uc
Electromagnetic compatibilityElectrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Resistance to fast transients2 kV IEC 61000-4-4 level 3
Disturbance radiated (conducted)CISPR 11 group 1 - class A CISPR 22 - class A
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) IEC 61000-4-3 level 3
Ambient air temperature for operation-4...149 °F (-20...65 °C)
Resistance to electrostatic discharge6 kV contact IEC 61000-4-2 level 3 8 kV air IEC 61000-4-2 level 3
MPN