Schneider Electric SEE116C03
MPNSEE116C03
Active
Acti9 - earth leakage circuit breaker - 1P+Ns - 16A - C - 30mA - 10000 A
$49.53Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC |
| Product or component type | Residual current breaker with overcurrent protection (RCBO) |
| Voltage | 400 V AC 50 Hz |
| [Ue] rated operational voltage | 150...230 V AC 50 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| [Icw] rated short-time withstand current | Icw: 250 A during 8/20 µs impulse withstand |
| Surge current | 250 A |
| Breaking capacity | 10000 A Icn at 150...230 V AC 50 Hz |
| Current | 16 A at 30 °C |
| Residual current tripping technology | Voltage dependent |
| Network frequency | 50 Hz |
All specifications
| Parameter | Value |
|---|---|
| Poles description | 1P + Ns |
| Number of protected poles | 1 |
| IP degree of protection | IP20 |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Wire stripping length | 14 mm for upstream connection 11 mm for downstream connection |
| Connections - terminals | Screw clamp terminal (upstream) 1...16 mm² rigid Screw clamp terminal (upstream) 1...16 mm² flexible Screw clamp terminal (downstream) 1...10 mm² rigid Screw clamp terminal (downstream) 1...10 mm² flexible |
| Relative humidity | 95 % at 55 °C |
| Depth | 70 mm |
| Width | 18 mm |
| Color | White |
| Height | 117 mm |
| Electrical durability | 10000 cycles |
| Mechanical durability | 20000 cycles |
| Standards | IEC 61009-2-2 IEC 61009-1 |
| Range | Acti9 |
| Curve code | C |
| 9 mm pitches | 2 |
| Tropicalisation | 2 |
| Limitation class | 3 |
| Local signalling | ON/OFF indication |
| Neutral position | Left |
| Targeted country | UK |
| Device short name | iC60N RCBO |
| Tightening torque | 2 N.m upstream 2 N.m downstream |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Integrated |
| Provision for padlocking | Padlockable |
| Earth-leakage sensitivity | 30 mA |
| Suitability for isolation | Yes |
| Contact position indicator | Yes |
| Circuit breaker application | Distribution |
| Electrical insulation class | Class III |
| Locking options description | By padlocks |
| Earth-leakage protection class | Type A |
| Ambient air temperature for storage | -30...70 °C |
| Earth-leakage protection time delay | Instantaneous |
| Ambient air temperature for operation | -25...55 °C |
| Comb busbar and distribution block compatibility | YES |
MPN