Schneider Electric VCF01GEGP
MPNVCF01GEGP
Active
TeSys Vario enclosed, emergency switch disconnector, 16A, IP65, groundplate
$88.35Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Control type | Rotary handle |
| Product or component type | Enclosed emergency stop switch disconnector |
| [Ue] rated operational voltage | 690 V AC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Icw] rated short-time withstand RMS current | 300 A at 400 V duration: 1 s |
| Breaking capacity | 200 A at 400 V (AC-21A) 200 A at 400 V (AC-22A) 200 A at 400 V (AC-23A) |
| [Ie] rated operational current | 11 A (AC-23A) at 400 V |
| Rated conditional short-circuit current | 10 kA at 400 V - associated fuse 20 A aM 10 kA at 400 V - associated fuse 20 A gG |
| [Icm] rated short-circuit making capacity | 1 kA at 400 V at Ipeak |
| [Ithe] conventional enclosed thermal current | 16 A |
| Rated operational power in | 5.5 kW at 400 V (AC-23) 4 kW at 400 V (AC-3) |
| Poles description | 3P |
All specifications
| Parameter | Value |
|---|---|
| Intermittent duty class | 30 |
| IP degree of protection | IP65 conforming to IEC 60529 |
| Connections - terminals | Power circuit: screw clamp terminals2.5...4 mm² - flexible - with cable end Protective earth: screw clamp terminals2.5...4 mm² - flexible - with cable end Shield cable earth: cable clips |
| Depth | 131 mm |
| Width | 90 mm |
| Height | 146 mm |
| Handle colour | Red |
| Handle front plate colour | Yellow |
| Handle front plate dimension | 60 x 60 mm |
| Electrical durability | 100000 cycles AC-21 30000 cycles DC-1...5 |
| Mechanical durability | 100000 cycles |
| Standards | IEC 60947-4-1 IEC 60204 |
| Range | TeSys |
| Marking | 0 - 1 |
| Fire resistance | 960 °C conforming to IEC 60595-2-1 |
| Device short name | VCF |
| Safety category | High performance |
| Tightening torque | 2.1 N.m - on screw clamp terminals |
| Protective treatment | TC |
| Mechanical robustness | Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6 Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27 |
| Making capacity ( i rms) | 200 A at 400 V AC-21A 200 A at 400 V AC-22A 200 A at 400 V AC-23A |
| Rotary handle padlocking | 1 to 3 padlocks 4...8 mm |
| Suitability for isolation | Yes |
| Environmental characteristic | Standard environment |
| Ambient air temperature for operation | -20...50 °C |
MPN