Skip to main content
Schneider Electric VW3A68501 — Motor Control Accessories

Schneider Altivar VW3A68501 Line Choke, 160 A, 0.22 mH

MPNVW3A68501
Active

Schneider Altivar series line choke, VW3A68501, 160 A rated current, 0.22 mH inductance, 3-phase 400/500 Vac, IP00/IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

VW3A68501 — Identification
ParameterValue
Product / component typeLine choke
Product rangeAltivar
VW3A68501 — Electrical
ParameterValue
Rated current (In)160 A
VW3A68501 — Cable & Connector
ParameterValue
Electrical connectionTerminal 6 mm² / AWG 8, 0.8...1 N.m
VW3A68501 — Mechanical
ParameterValue
Width280 mm
Height305 mm
Depth210 mm
VW3A68501 — Environmental
ParameterValue
IP protection ratingChoke: IP00 Terminals: IP20
Operating ambient temperature45...55 °C (with current derating of 2 % per °C) 0...45 °C (without current derating)
Storage ambient temperature-25...70 °C
Relative humidity0...95 %
Operating altitude1000...3000 m with current derating 1 % per 100 m
Environmental class3B1 conforming to IEC 721-3-3 3C2 conforming to IEC 721-3-3 3S1 conforming to IEC 721-3-3
VW3A68501 — Approvals
ParameterValue
Conformance standardsVDE 0160 level 1 EN 50178 IEC 60076 (with HD398)

Product details

What this line choke does

The Schneider Altivar VW3A68501 is a 3-phase line choke rated for 160 A continuous current, with 0.22 mH inductance, designed for 400/500 Vac mains supplies. Its primary job is reducing current harmonics drawn by variable-frequency drives — it sits between the mains and the drive input, smoothing the current waveform and limiting harmonic distortion that would otherwise stress upstream transformers and trip nuisance breakers.

Rated 160 A (In) continuous. That's the current the choke can carry indefinitely at rated conditions — size it for the drive's input current, not the motor nameplate. For overloads, it handles 1.65 × In for 60 seconds, which covers the typical inrush and acceleration peaks on a standard VFD. Voltage drop at rated load is 5 %, which is typical for a line choke of this size and inductance. That drop is predictable and the drive compensates for it; what matters is the choke's impedance limiting the rate of rise of fault current and smoothing the rectifier's current pulses. Thermal losses of 220 W at rated current. The choke is Class F insulated (155 °C hot-spot rating), so it can run warm, but the surrounding air temperature must stay within the derating curve: 0 to 45 °C without derating, 45 to 55 °C with a 2 % per °C current reduction. Altitude derating: from 1000 to 3000 m, reduce current 1 % per 100 m. Above 3000 m, the air density is too low for reliable convection cooling — consult the drive application manual if you're working above that.

The terminals are IP20 (finger-safe). Dimensions: 280 mm wide, 305 mm tall, 210 mm deep. That's a substantial block; confirm your panel's backplate space and the gland-plate clearance for the incoming cables. Electrical connection is via a 6 mm² / AWG 8 terminal, torque 0.8 to 1.0 N·m. That's sized for the 160 A rating — you'll need parallel cables or larger lugs if your run is long; the terminal itself is the bottleneck only for the connection point. Environmental class per IEC 721-3-3: 3B1 (moderate biological), 3C2 (moderate chemical), 3S1 (low mechanical active contaminants). That's a standard industrial panel environment — not for outdoor, washdown, or corrosive atmospheres without additional enclosure protection.

Designed to VDE 0160 level 1, EN 50178 (electronic equipment for power installations), and IEC 60076 (power transformers, with HD398). Clearance distance 5.5 mm, creepage 11.5 mm per IEC 60664, pollution degree 2. These are the insulation coordination standards that let it sit on a 400/500 V mains circuit without flashover. Shock rated 15 gn for 11 ms per IEC 60068-2-27; vibration 1 gn at 13-200 Hz and 1.5 mm peak-to-peak at 3-13 Hz per IEC 60068-2-6. That's standard for fixed industrial installation — not for mobile or shipboard without additional qualification. No end-of-life notice or successor part has been issued. This is a current-production item in the Altivar accessory range.

Frequently asked questions

What is the lead time for VW3A68501?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for VW3A68501?

The choke is designed to VDE 0160 level 1, EN 50178, and IEC 60076 (with HD398). Clearance and creepage distances follow IEC 60664 for pollution degree 2. RoHS and REACH declarations are typically included with the shipment from Schneider; confirm with your order if a specific certificate is required.

MPN
VW3A68501