Schneider VW3A7106 Braking Resistor
MPNVW3A7106
Active
Square D VW3A7106 Resistance Braking U|Square D VW3A7106 Resistance Braking U
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Protection type | Integrated thermal protection thermal probe |
| Maximum DC bus voltage | 450 V |
| Maximum braking power | 80 kW |
| Permanent braking power | 60 kW at constant power and at engage threshold) |
| IP degree of protection | IP20 IP21 on top) |
| Operating altitude | 3280.84...13123.36 ft (1000...4000 m) with current derating 1 % per 100 m |
| Depth | 11.9 in (303 mm) |
| Width | 8.5 in (216 mm) |
| Height | 25.9 in (658 mm) |
| Category | US1CP4E22278 |
| Load factor | 0.05 150 kW at constant power and at engage threshold 0.15 120 kW at constant power and at engage threshold 0.5 95 kW at constant power and at engage threshold 1 75 kW at constant power and at engage threshold |
| Thermal losses | 400 W |
All specifications
| Parameter | Value |
|---|---|
| Operating position | Vertical +/- 10 degree |
| Activation threshold | 395 V DC +/- 1 % |
| Mechanical robustness | Vibrations class 3M4 IEC 60721-3-3 |
| Volume of cooling air | 43853.3 Gal/hr(US) (166 m3/h) |
| Ambient air temperature for storage | -40...158 °F (-40...70 °C) |
| Minimum resistor value to associate | 1.4 Ohm |
| Ambient air temperature for operation | 14...122 °F (-10...50 °C) |
MPN