Skip to main content
Schneider Electric VW3A7257 — Motor Control Accessories

Schneider Electric VW3A7257 Active Infeed Converter, 540 kW

MPNVW3A7257
Obsolete

Schneider Electric VW3A7257 active infeed converter (AIC), 540 kW, 380-440 V AC, 815 A continuous output, IP00, built-in unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

VW3A7257 — Electrical
ParameterValue
Network frequency50/60 Hz
VW3A7257 — Cable & Connector
ParameterValue
Connector type1 RJ45 for Modbus Male SUB-D 9 on RJ45 for CANopen
VW3A7257 — Mechanical
ParameterValue
Width880 mm
Height1150 mm
Depth377 mm
VW3A7257 — Environmental
ParameterValue
IP protection ratingIP00
Operating ambient temperature45...60 °C (with current derating of 2 % per °C) -10...45 °C
Storage ambient temperature-25...70 °C
Relative humidity0...95 %
Operating altitude1000...3000 m with current derating 1 % per 100 m
Environmental class3K3 conforming to EN/IEC 60721-3-3 3C2 conforming to EN 60721-3-3 3S2 conforming to EN 60721-3-3
VW3A7257 — Approvals
ParameterValue
Conformance standardsEN/IEC 61800-5-1

Product details

Active infeed converter — 540 kW, 380-440 V

The VW3A7257: It draws 780 A line current at 400 V and handles overloads up to 1.20× nominal for 60 s or 1.35× nominal for 2 s. This unit is designed for energy regeneration and low-harmonics applications — it's the front-end converter that conditions the DC bus for a drive system, not a standalone drive itself.

Schneider Electric lists the VW3A7257 as obsolete (mature stage). No official successor part number is recorded.

Physical footprint and mounting

The built-in unit measures 880 mm wide × 1150 mm high × 377 mm deep — a substantial cabinet footprint. It requires 1500 cm² of air-flow surface and moves 1800 m³/h of cooling air for the power circuit plus 500 m³/h for the control circuit via forced convection. Operating position is vertical ±10°, and the unit is rated IP00 — it must be installed inside a suitable enclosure that provides the required ingress protection and clearance for the 8920 W of thermal losses.

Environmental and compliance

Designed to EN/IEC 61800-5-1 with pollution degree 2. Ambient operating range is -10 to 45 °C, with derating up to 60 °C (2 % per °C above 45 °C). Storage range is -25 to 70 °C. Altitude derating applies above 1000 m (1 % per 100 m up to 3000 m). Environmental classification is 3K3 (temperature/humidity), 3C2 (chemical), 3S2 (mechanical) per EN/IEC 60721-3-3. Vibration resistance is 1.5 mm at 3-10 Hz and 0.6 gn at 10-200 Hz; shock resistance is 4 gn for 11 ms.

Communications and control interface

The unit includes a communication bridge option card with one RJ45 for Modbus and a male SUB-D 9 on RJ45 for CANopen. Protocol support covers Modbus and CANopen.

Frequently asked questions

What is the VW3A7257 used for?

It is an active infeed converter (AIC) rated 540 kW at 400 V, used for energy regeneration and low-harmonics front-end conditioning of the DC bus in drive systems. It is not a standalone drive.

What are the key electrical ratings of VW3A7257?

Continuous output current is 815 A at 400 V. Line current is 780 A at 400 V. Overload capability is 1.20× nominal for 60 s and 1.35× nominal for 2 s. Input voltage range is 380-440 V AC ±10 %, 3-phase, 50/60 Hz.

MPN
VW3A7257