Skip to main content
Schneider Electric VW3A7276 — Motor Control Accessories

Schneider Electric VW3A7276 Active Infeed Converter, 540 kW

MPNVW3A7276
Obsolete

Schneider Electric VW3A7276 active infeed converter (AIC), 540 kW, 500-690 V AC, 3-phase, IP00, forced convection cooling, built-in unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

VW3A7276 — Electrical
ParameterValue
Network frequency50/60 Hz
VW3A7276 — Cable & Connector
ParameterValue
Connector type1 RJ45 for Modbus Male SUB-D 9 on RJ45 for CANopen
VW3A7276 — Mechanical
ParameterValue
Width1110 mm
Height1390 mm
Depth377 mm
VW3A7276 — Environmental
ParameterValue
IP protection ratingIP00
Operating ambient temperature45...60 °C (with current derating of 2 % per °C) -10...45 °C
Storage ambient temperature-25...70 °C
Relative humidity0...95 %
Operating altitude1000...2400 m with current derating 1 % per 100 m
Environmental class3K3 conforming to EN/IEC 60721-3-3 3C2 conforming to EN 60721-3-3 3S2 conforming to EN 60721-3-3
VW3A7276 — Approvals
ParameterValue
Conformance standardsEN/IEC 61800-5-1

Product details

What this AIC delivers and where it fits

The VW3A7276 is a 540 kW active infeed converter (AIC) designed for 500-690 V AC three-phase networks. It's the front-end power stage for energy regeneration and low-harmonic operation in a Schneider Active Front End system, feeding DC bus voltages up to 1100 V DC from a 690 V AC supply. Continuous output current is 481 A across the full voltage range, with overload capability of 1.2× nominal for 60 seconds or 1.35× for 2 seconds. Input power capability scales with line voltage: 390 kW at 500 V, 468 kW at 600 V, 536 kW at 690 V. Built-in unit, IP00, forced-convection cooled — the 7730 W thermal loss demands 2400 m³/h airflow over the power circuit and 260 m³/h for the control section, with a minimum 2000 cm² air flow surface. This is not a standalone cabinet; it's a panel-mounted component that needs engineered ventilation.

Lifecycle reality — obsolete, sourced on request

Schneider Electric lists the VW3A7276 as obsolete. For production or MRO requirements, the unit is sourced through independent distribution channels — availability and pricing confirmed at RFQ against the specific line-item need. Compliance documentation covers EN/IEC 61800-5-1 for adjustable-speed drive safety. Environmental classification is 3K3/3C2/3S2 per EN/IEC 60721-3-3, and pollution degree 2 per EN 61800-5-1. Storage temperature range is -25 to 70 °C.

Dimensions and integration constraints

Footprint is 1110 mm wide × 1390 mm high × 377 mm deep. Operating position must be vertical within ±10 degrees. Shock resistance is 4 gn for 11 ms; vibration tolerance is 1.5 mm at 3-10 Hz and 0.6 gn at 10-200 Hz, per EN/IEC 60068-2-6. Communication bridge option card provides one RJ45 for Modbus and one male SUB-D 9 on RJ45 for CANopen. The line current draw is 450 A at all rated voltages.

Frequently asked questions

What are the key electrical ratings for VW3A7276?

Continuous output current is 481 A at 500 V, 600 V, and 690 V. Input power capability: 390 kW at 500 V, 468 kW at 600 V, 536 kW at 690 V. Overload: 1.2× nominal for 60 s, 1.35× for 2 s. DC bus output: up to 1100 V DC from a 690 V AC supply.

What compliance standards does VW3A7276 meet?

It complies with EN/IEC 61800-5-1 for drive safety, pollution degree 2, and environmental classes 3K3, 3C2, 3S2 per EN/IEC 60721-3-3. The IP rating is IP00 — no ingress protection, so it requires enclosure mounting.

MPN