Skip to main content
Siemens 3RH1131-1AF00 — Contactors

Siemens 3RH1131-1AF00 SIRIUS Auxiliary Contactor, 3 NO + 0 N

MPN3RH1131-1AF00

Siemens SIRIUS auxiliary contactor, size S00, 3 NO instantaneous contacts, 45 mm width, screw and snap-on mounting, IP20 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RH1131-1AF00 — Identification
ParameterValue
Contactor frame sizeS00
3RH1131-1AF00 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 110 V1 A
Rated value @ 220 V0.27 A
3RH1131-1AF00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz110 V
3RH1131-1AF00 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH1131-1AF00 — Connection & Mounting
ParameterValue
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting
3RH1131-1AF00 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RH1131-1AF00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH1131-1AF00 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

The Siemens 3RH1131-1AF00 is a SIRIUS auxiliary contactor in size S00, carrying three normally-open instantaneous contacts and no delayed or lagging switching. The IP20 front protection means it is intended for installation inside an enclosure, not for exposed washdown areas.

Switching capacity and contact reliability

Rated for 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — these are the thermal current limits for the NO contacts under AC duty. The contact reliability spec calls for one incorrect switching operation per 100 million cycles at 17 V, 1 mA, which is a standard figure for dry-circuit signal switching in PLC or relay logic.

Screw terminals accept solid conductors: 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), or 2x 4 mm². Shock resistance is 10g / 5 ms and 5g / 10 ms.

Frequently asked questions

Where can I buy 3RH1131-1AF00 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 3RH1131-1AF00's listed depth?

The depth is 72 mm, with a width of 45 mm and height of 57.5 mm.

What wire sizes does the 3RH1131-1AF00 accept?

Solid conductors: 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), or 2x 4 mm² per terminal.

What compliance documentation does this brand provide for 3RH1131-1AF00?

The substance prohibition date of 01.07.2006 confirms RoHS compliance per Directive 2002/95/EC. The reference code per IEC 81346-2 is K.

MPN
3RH1131-1AF00