It mounts on a 35 mm DIN rail via screw or snap-on fastening, with a depth of 73 mm, width of 90 mm, and height of 57.5 mm — the standard S00 footprint that slides into any panel already laid out for this frame size.
Each NO contact is rated 10 A at 24 V AC (50/60 Hz) and also 10 A at 230 V AC — that's the resistive load curve the contact can handle continuously. At higher voltages the current drops: 3 A at 400 V, 1 A at 690 V, and for DC switching you get 10 A at 24 V, 4.7 A at 60 V, down to 0.26 A at 600 V. The arcing time sits between 10 and 15 ms, which is typical for a contactor of this class and tells you the contact gap clears the arc fast enough for most control circuits. Mechanical service life is 5 million operations typical — that's the number of times the armature can cycle before wear becomes a concern.
Mounting and wiring flexibility
Wire terminations accept 2x 0.5 to 1.5 mm², 2x 0.75 to 2.5 mm², or 2x 4 mm² solid or stranded.