Panel integration — S0 frame, spring terminals, DIN rail
With a width of 45 mm, height of 102 mm, and depth of 144 mm, it fits standard panel layouts and leaves room for adjacent devices at the specified clearances: 10 mm upwards, 10 mm forwards, 10 mm downwards, and 6 mm to the side. The magnet coil uses spring-type terminals, accepting solid or stranded conductors from 1 to 10 mm², or two conductors 0.5 to 2.5 mm² each.
Rated switching performance and duty cycles
The AC-3 maximum switching frequency is 750 cycles per hour, while AC-4 (plugging/reversing) is limited to 250 cycles per hour. For resistive loads (AC-1), it can switch up to 1,000 cycles per hour. For DC switching, the contactor is rated at 6 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 0.6 A at 440 V — useful for DC motor braking or auxiliary circuits. The arcing time is 10 to 10 ms at AC, and the coil draws 0.25 A at 50 Hz.