Duty-cycle and switching frequency
Rated for up to 1 000 switching cycles per hour at AC-1 (resistive load), 750/h at AC-2 and AC-3 (motor starting and running), and 250/h at AC-4 (plugging/inching). The AC-3e rating also sits at 750/h.
The built-in auxiliary switch is rated at 10 A at 24 V, 2 A at 48 V or 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.6 A at 440 V — covers most control-voltage levels in a panel.
Conductor cross-section accepts solid or stranded 1…10 mm², or 2x (0.5…2.5 mm²) for the auxiliary circuit.