Skip to main content
Siemens 3VA1050-2ED32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-2ED32-0AH0 SENTRON MCCB, 50 A, 52.5 kA

MPN3VA1050-2ED32-0AH0

Siemens SENTRON 3VA1050-2ED32-0AH0, molded case circuit breaker (MCCB), 3-pole, 50 A rated current, 52.5 kA interrupting capacity at 240 V, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1050-2ED32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10502ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1050-2ED32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.14.6 W
3VA1050-2ED32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1050-2ED32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1050-2ED32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1050-2ED32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1050-2ED32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1050-2ED32-0AH0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, carrying a 50 A rated current at 40 °C and a 52.5 kA breaking capacity at 240 V. The TM210 overcurrent release handles the thermal-magnetic trip curve, so the breaker responds to sustained overloads (thermal) and short-circuit events (magnetic) in a single unit.

The interrupting capacity drops as the system voltage rises: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

Rated current holds at 50 A from 40 °C through 50 °C ambient, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.

Auxiliary contacts and signaling

The trip indicator is present, so a visual flag confirms the breaker tripped on fault rather than being manually opened.

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint for DIN-rail or panel-mount installation.

Frequently asked questions

How do I get pricing and availability for 3VA1050-2ED32-0AH0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of 3VA1050-2ED32-0AH0 at different voltages?

52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

What is the rated current of 3VA1050-2ED32-0AH0 at elevated ambient temperatures?

50 A from 40 °C to 50 °C, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.

What auxiliary switches come with 3VA1050-2ED32-0AH0?

2 auxiliary switches plus 1 trip alarm switch (HQ), providing three independent status feedback paths.

MPN
3VA1050-2ED32-0AH0