Siemens 3VA1050-3ED32-0AD0 — 50 A SENTRON MCCB with TM210 Release
It carries 75.6 kA interrupting capacity at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — figures that define its fault-clearing capability at the panel's service voltage. The TM210 release is a fixed, non-adjustable thermal-magnetic trip unit — no field-configurable long-time or short-time pickup. That makes this a line-protection breaker for straightforward feeder or branch circuits where coordination studies don't require adjustable trip settings.
Above that, the continuous current must be derated: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.
For frequent switching duty, consider a contactor ahead of this MCCB.