Rated 50 A continuously from 40 °C up to 50 °C ambient, derating to 45 A at 70 °C. Breaking capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — enough for high-fault utility feeds without cascading upstream breakers.
Footprint is 76.2 mm wide (3 in), 130 mm tall, and 70 mm deep — fits standard Siemens 3VA panel cutouts and busbar systems without adapter plates. Max power dissipation is 17.1 W — account for that heat load when spacing breakers in a sealed enclosure.