What the 220 kA breaking capacity means for your panel
What sets it apart is the interrupting capacity: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V.
The 3VA1104-6MG36-0AA0 measures 70 mm deep by 76.2 mm wide by 130 mm high — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures. The optional motor drive (Product Extension / Optional / Motor Drive: Yes) allows remote closing or opening via a separate accessory — useful for automated restart schemes.
Release and protection characteristics
The TM110M overcurrent release is a fixed thermal-magnetic type: the thermal element protects against overloads (4 A continuous), and the magnetic element trips instantaneously on short-circuit at a fixed threshold of 64 A (li min. and li max. both 64 A). That means the magnetic pickup is not adjustable — if your motor inrush exceeds 64 A, this breaker will nuisance-trip on start.