Skip to main content
Siemens 3VA1132-3ED36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-3ED36-0AA0 SENTRON MCCB, 32A 3-Pole, TM210

MPN3VA1132-3ED36-0AA0
Active

Siemens SENTRON 3VA1132-3ED36-0AA0, molded case circuit breaker, 3-pole, 32 A (40 °C), TM210 thermal-magnetic release, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1132-3ED36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1132-3ED36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W
3VA1132-3ED36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1132-3ED36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-3ED36-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1132-3ED36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-3ED36-0AA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The TM210 thermal-magnetic release handles overload and short-circuit protection — the adjustable short-circuit release (Ii) maxes out at 320 A, letting you fine-tune coordination downstream.

This MCCB's interrupting ratings span the common industrial voltages: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V.

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a compact 3-pole footprint that drops into standard MCCB mounting bases. Front IP40 protection is adequate for enclosed panel mounting; no washdown rating, so keep it behind the gland plate.

Frequently asked questions

Where can I buy 3VA1132-3ED36-0AA0 and how is it quoted?

This MCCB is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not a stock promise.

What are the key interrupting ratings for 3VA1132-3ED36-0AA0?

At 240 V it interrupts 75.6 kA; at 415 V, 52.5 kA; at 440 V, 32 kA; at 500 V and 690 V, 11.9 kA. These cover most industrial distribution and motor control applications.

What compliance documentation is available for this SENTRON MCCB?

As a Siemens SENTRON product, it carries IEC 60947-2 certification. RoHS and REACH compliance documentation is standard with the brand. Specific UL listing status should be confirmed against the exact variant code.

MPN
3VA1132-3ED36-0AA0