The TM210 thermal-magnetic release handles overload and short-circuit protection — the adjustable short-circuit release (Ii) maxes out at 320 A, letting you fine-tune coordination downstream.
This MCCB's interrupting ratings span the common industrial voltages: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V.
Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a compact 3-pole footprint that drops into standard MCCB mounting bases. Front IP40 protection is adequate for enclosed panel mounting; no washdown rating, so keep it behind the gland plate.